Dealing with malfunctions

Fault code A-01 on the numerical 

display

 Indication  that  the  air  filter  needs  to  be  cleaned 
(error code is shown every third month).

When the filter has been cleaned reset the fault code 
by turning the heat pump off and on again.

Fault code A-03 on the numerical 

display

A  high  pressure  or  low  pressure  pressostat  in  the 

refrigerant circuit has tripped, see the section Reset-

ting pressostats.

 High pressure pressostat (33): 

Settings for Heat-

ing  curve  selection  (37)  and  Heating  curve  offset 

(38) too high (can also be seen on Channels 6 and 

7 on the numerical display). Also see section Room 

temperature.

 Low pressure pressostat (41): 

The fan is not run-

ning or too little refrigerant

When  the  cause  of  the  fault  has  been  put  right,  the 

fault code must be cleared from the display by switch-

ing the heat pump off and on again.

Middle lamp lit

 Defrosting. 

When there is too much ice on the evaporator, defrost-

ing takes place. After this, the compressor starts auto-

matically if heating is needed. Frequent defrosting is a 

sign of clogged ventilation or dirty filters. See the sec-

tion, Maintenance routines — Cleaning the air filter.

Indications on the display

NOTE! 

This fault state must not be repeatedly 

reset, this will bring about a risk for 

freezing of the supply air battery.

Fault code A-02 on the numerical 

display

Frost  guard  tripped  due  to  a  too  low  supply  air  tem-
perature. Risk for freezing of the supply air battery.

Incorrect setting on the curve slope and offset

   Air in the supply air battery (see the section Supply 

air battery)

   Low  availability  on  the  supplementary  power  (e.g. 

block immersion heater), see the section, Functions 
on the front panel.

When  the  cause  of  the  fault  has  been  put  right,  the 
fault code must be cleared from the display by switch-
ing the heat pump off and on again.

Fault code A-11

When  codes  A-03  and  A-01  are  active  at  the  same 
time, this code is displayed.

25

For the Installer

FIGHTER 410P

The miniature circuit-breaker (7) is accessible behind 
the upper front access panel and is located to the left 
of the panel.
Normal mode of the miniature circuit-breaker is 

1

 (up).

Resetting the miniature circuit 

breakers

Art.nr.  611822

2

1

bar

3

0

4

2

1

bar

3

0

4

2

1

bar

3

0

4

Transparent, blåfärgad film (ej hål).

67,5

57.25

26,3

86,3

92,7

126,8

129,8

132,8

145,2

336

41

19,2

83

90.5

111

98,6

523

10,5

Ø 52,8

53,5

135,3

130,7

15

70,5

135,3

r=4,5

37

23

9

2 st Ø 4,5, transparent, ofärgad film (ej hål).

OBS! Endast halv cirkel (radie=11)

Slits på baksidan

De 8 grårastrerade ytorna (Ø22)
skall ej förses med häftämne.

49,5

84,4

85,7

186,3

196,8

42,5

52

 161

Ø 13

Ø 18,5

Hål 16 x 31

Hål 16 x 16

313,2

Art.nr.  611822

2

1

bar

3

0

4

2

1

bar

3

0

4

2

1

bar

3

0

4

Transparent, blåfärgad film (ej hål).

67,5

57.25

26,3

86,3

92,7

126,8

129,8

132,8

145,2

336

41

19,2

83

90.5

111

98,6

523

10,5

Ø 52,8

53,5

135,3

130,7

15

70,5

135,3

r=4,5

37

23

9

2 st Ø 4,5, transparent, ofärgad film (ej hål).

OBS! Endast halv cirkel (radie=11)

Slits på baksidan

De 8 grårastrerade ytorna (Ø22)
skall ej förses med häftämne.

49,5

84,4

85,7

186,3

196,8

42,5

52

 161

Ø 13

Ø 18,5

Hål 16 x 31

Hål 16 x 16

313,2

Art.nr.  611822

2

1

bar

3

0

4

2

1

bar

3

0

4

2

1

bar

3

0

4

Transparent, blåfärgad film (ej hål).

67,5

57.25

26,3

86,3

92,7

126,8

129,8

132,8

145,2

336

41

19,2

83

90.5

111

98,6

523

10,5

Ø 52,8

53,5

135,3

130,7

15

70,5

135,3

r=4,5

37

23

9

2 st Ø 4,5, transparent, ofärgad film (ej hål).

OBS! Endast halv cirkel (radie=11)

Slits på baksidan

De 8 grårastrerade ytorna (Ø22)
skall ej förses med häftämne.

49,5

84,4

85,7

186,3

196,8

42,5

52

 161

Ø 13

Ø 18,5

Hål 16 x 31

Hål 16 x 16

313,2

Art.nr.  611822

2

1

bar

3

0

4

2

1

bar

3

0

4

2

1

bar

3

0

4

Transparent, blåfärgad film (ej hål).

67,5

57.25

26,3

86,3

92,7

126,8

129,8

132,8

145,2

336

41

19,2

83

90.5

111

98,6

523

10,5

Ø 52,8

53,5

135,3

130,7

15

70,5

135,3

r=4,5

37

23

9

2 st Ø 4,5, transparent, ofärgad film (ej hål).

OBS! Endast halv cirkel (radie=11)

Slits på baksidan

De 8 grårastrerade ytorna (Ø22)
skall ej förses med häftämne.

49,5

84,4

85,7

186,3

196,8

42,5

52

 161

Ø 13

Ø 18,5

Hål 16 x 31

Hål 16 x 16

313,2

Art.nr.  611822

2

1

bar

3

0

4

2

1

bar

3

0

4

2

1

bar

3

0

4

Transparent, blåfärgad film (ej hål).

67,5

57.25

26,3

86,3

92,7

126,8

129,8

132,8

145,2

336

41

19,2

83

90.5

111

98,6

523

10,5

Ø 52,8

53,5

135,3

130,7

15

70,5

135,3

r=4,5

37

23

9

2 st Ø 4,5, transparent, ofärgad film (ej hål).

OBS! Endast halv cirkel (radie=11)

Slits på baksidan

De 8 grårastrerade ytorna (Ø22)
skall ej förses med häftämne.

49,5

84,4

85,7

186,3

196,8

42,5

52

 161

Ø 13

Ø 18,5

Hål 16 x 31

Hål 16 x 16

313,2

Art.nr.  611603

2

1

bar

3

0

4

2

1

bar

3

0

4

2

1

bar

3

0

4

Transparent, blåfärgad film (ej hål).

18,6

98,1             

26,3

4,2

86,3

92,7

126,8

129,8

132,8

145,2

272,5

336

41

19,2

83

90.5

111

98,6

523

10,5

Ø 52,8

53,5

135,3

130,7

15

70,5

135,3

261,5

r=4,5

37

23

9

2 st Ø 4,5, transparent, ofärgad film (ej hål).

OBS! Endast halv cirkel (radie=11)

Slits på baksidan

De 8 grårastrerade ytorna (Ø22)
skall ej förses med häftämne.

49,5

84,4

85,7

186,3

196,8

42,5

67,5

57,25

52

 161

Ø 13

Ø 18,5

Ø 62

Hål 16 x 31

Hål 16 x 16

313,2

 2 st urstansninga , bredd=5 och r=2,5

Summary of Contents for FIGHTER 410P

Page 1: ...INSTALLATION AND MAINTENANCE INSTRUCTION FIGHTER 410P 230V MOS GB 0823 2 FIGHTER 410P 511379 L E K...

Page 2: ...LEK LEK 1 2 LEK LEK 1 3 4 5...

Page 3: ...trol system Heating curve offset 2 22 Heating curve offset 0 22 Heating curve offset 2 22 Setting with diagrams 22 Service Opening the front panel 23 Refrigerant system 23 Channel description 23 Deali...

Page 4: ...sure 16 bar Immersion heater R50 8000W 230 V Operating pressure tap water 6 bar Expansion vessel tap water charge pressure 3 5 bar Expansion vessel heating water charge pressure 0 5 bar Pressure reduc...

Page 5: ...valve where the pressure and temperature are further reduced The refrigerant has now completed its circulation and returns to the evaporator A frost protection damper precedes the supply air side s h...

Page 6: ...Upper visible part of the front panel Numerical display Art nr 611822 2 1 bar 3 0 4 2 1 bar 3 0 4 2 1 bar 3 0 4 41 19 2 83 90 5 111 98 6 523 15 70 5 135 3 Switch Pressure gauge Indicator lamps Extra...

Page 7: ...tandby mode to normal mode 1 the numerical display can remain dimmed for a brief period This can also occur at extremely low outdoor tem peratures Extra hot water Pressing the Extra hot water button r...

Page 8: ...1 bar 3 0 4 111 523 Front panel FIGHTER 410P For Home Owners 6 Lower hidden part of the front panel Indicator lamps Heating curve selection Operating mode Channel selection I H J G L Miniature circuit...

Page 9: ...always shows channel 1 When you have browsed through the channels channel 1 returns after a while Heating curve selection Use the Heating curve selection knob to set the automatic heating control syst...

Page 10: ...eratures have time to stabilise Readjustment of basic settings Cold weather conditions If the room temperature is low increase the heating curve selection setting by one step If the room temperature i...

Page 11: ...Assembly takes place in the reverse order Every third month a reminder for cleaning the filter is shown in the display as A 01 Note that the time will be set to zero by setting the switch to 0 Cleani...

Page 12: ...eck one valve at a time as follows Open the valve Check that water flows through the valve Close the valve The heating system may need to be refilled after checking the safety valve 52 see the section...

Page 13: ...nd the highest radiator is 5 metres see figure If the standard initial pressure in the pressure vessel is not high enough it can be increased by adding air via the valve in the expansion vessel The in...

Page 14: ...Discharge pipes from tundishes shall have av vertical section of pipe at least 300 mm long before any elbows or bends in the pipework See following picture General If the vertical distance 300 mm is...

Page 15: ...kapacitet Fl de Tillg ngligt tryck kPa Internt tryckfall i panna inklusive armatur Tillg nglig pumpkapacitet pannans interntryckfall fr ndraget kPa 4 l h P 5 6 3 2 wg 10 200 0 0 20 400 30 600 40 800 5...

Page 16: ...e supply air battery is connected in parallel with the radiator circuit and heats the house s supply air The addi tional output is determined according to the diagram The water flow through the supply...

Page 17: ...ould not be changed In position A reduced position a low exhaust air respective supply air flow should be obtained How low is determined in each specific case NOTE The exhaust air flow must never drop...

Page 18: ...rthed This is done by making a sound electrical connection to the four ventilation ducts using the four earthing cables supplied The cables must then be connected to the earthing studs on top of the t...

Page 19: ...nging the output Connection Power rating as set at the factory NOTE Reset the temperature limiter it may have tripped during transport NOTE The switch 8 must not be moved from 0 until the boiler has b...

Page 20: ...ion B normal White cable 099 Exhaust air fan position C forced NOTE The same outlet must never be used for both fans Setting the fan capacity black white black white black white Normally the immersion...

Page 21: ...effektvakt 14 Rundstyrning RS och effektvakt EV Brytande kontaktfunktion RS EV EV RS SKYDDSKLENSP NNING SELV 1 2 3 4 5 6 7 8 ROMF LER RUNDSTYRING B R ER A B UTEF LER A Rundstyring eller belastningsvak...

Page 22: ...en it is opened for the first time Vent the FIGHTER through the safety valve 52 Other heating systems are vented using their respective venting screws Keep topping up and venting until all air has bee...

Page 23: ...in valve 51 using an R15 1 2 hose coupling Remove the cover 80 from the valve Now screw on the hose cou pling and open valve 51 Open safety valve 52 to let air into the system Draining the heating sys...

Page 24: ...RVA 2 V RMEKURVA 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 30 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1514 13 12 11 10 8 7 6 5 4 3 2 1 40 C UTETEMPERATUR 10 0 10 5 5 30 40 50 6...

Page 25: ...ual value 03 Outside temperature Actual value 04 Evaporation temperature Actual value 05 Extract air temperature Actual value 06 Curve slope Heating curve selection 07 Offset Heating curve offset 08 T...

Page 26: ...ion of a qualified installer Wrong operating mode selected with button 25 Closed or throttled filler valve 46 on the water h e a t e r Low temperature or a lack of hot water Circuit or main MCB trippe...

Page 27: ...efrosting is a sign of clogged ventilation or dirty filters See the sec tion Maintenance routines Cleaning the air filter Indications on the display NOTE This fault state must not be repeatedly reset...

Page 28: ...the fan this may need cleaning Contact your installer Cleaning the fan Luftningsskruv 16 Luftningsskruv 16 LEK LEK G RU N DFOS Type UPS 25 60 130 P N 59526447 230V PC 0017NIB 50Hz IP 44 TF 110 Class H...

Page 29: ...ge 0 27 26 169 28 15 14 5 41 40 39 38 37 36 35 Re 1 Re 2 Re 3 Re 4 Re 5 Re 6 Re 7 29 230 V 12 V B1 C1 34 Brun Bl Svart VR1 C2 C3 F3 F1 F2 C4 L2 L1 5 2 1 3 4 P3 P1 P2 1 2 3 4 5 6 7 8 6 0 kW 1 Noll ble...

Page 30: ...465 93 92 90 91 Skyddsklensp nning 16 Elektrisk matning 25 Dockning 16 A B och C Se Anslutning i Komponentlista Inom punktmarkerat omr de kan r rdragning fr n golv ej ske 70 A free space of 500 mm is...

Page 31: ...v k v 2 1 bar 3 0 4 LEK FILTER FILTER 6 7 107 145 8 78 9 16 17 18 1 25 31 32 30 41 44 19 27 33 37 38 39 40 42 44 35 73 152 50 80 14 109 53 55 56 58 59 68 11 65 70 103 71 148 150 47 51 85 88 89 96 82...

Page 32: ...ssories LEK 10 3 107 67 10 3 107 67 8 2 54 28 57 29 72 22 Top cabinet 245 mm Part no 089 424 Top cabinet 345 mm Part no 089 426 Top cabinet 385 535 mm Part no 089 428 Top cabinet A top cabinet is avai...

Page 33: ...t air Filter type G2 64 Drawing magnet supply air damper 65 Drying filter with tank 66 Air filter supply air Filter type G2 67 Contactor step 2 68 Docking pipe For the Installer 31 Connection Setting...

Page 34: ...e installed 47 50 dBA Height excl foot 15 40 mm 2 095 mm Width 600 mm Weight 200 kg Volume double jacket 70 litres Supply voltage 230 V 1 phase N Rated output circulation pump 100 W Rated output suppl...

Page 35: ......

Page 36: ...LLEMSTAD NB Tel 0168 477722 Fax 0168 476998 E mail info nibenl nl www nibenl nl V lund Varmeteknik Filial af NIBE AB Brog rdsvej 7 6920 Videb k Tel 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk...

Reviews: