Electrical connections

17

For the Installer

FIGHTER 410P

All electrical equipment except for the outdoor sensor 
has been connected at the factory.
Disconnect the heat pump before insulation testing the 
house wiring.

The  supply  to  the  heat  pump  is  connected  to  termi-
nal (9) via a strain relief. Connection must not be car-
ried out without the permission of the electricity sup-
plier  and  under  the  supervision  of  a  qualified  electri-
cian. The cable entry conduit is dimensioned for cable 
with a max Ø 19 mm.
The power is controlled via a contactor which is oper-
ated by a microprocessor.
The temperature limiter (6) cuts off the supply to the 
immersion heater if the temperature rises to 88 °C; it 
can be manually reset by pressing the button on the 
temperature limiter.
The temperature limiter (169) for the compressor cuts 

off  the  supply  to  the  compressor  if  the  temperature 

rises to 88 °C; it can be manually reset by pressing the 

button on the temperature limiter.

As standard the output power of the immersion heater 
is 8.0 kW. The supplied output is 6.0 kW.
Switching between different power outputs is done by 
opening the front panel (see under Service — Open-
ing  the  front  panel),  and  moving  certain  cables  as 
described  under  Electrical  diagram  —  Changing  the 
output.

Connection

Power rating as set at the 

factory

NOTE!

Reset the temperature limiter,  

it may have tripped during transport.

NOTE! 

The switch  (8) must not be moved 

from  “0” until the boiler has been 

filled with water. The temperature 

limiter, thermostat, compressor and 

the immersion heater can otherwise  

be damaged.

The  automatic  heating  control  system,  circulation 
pump (16) and its cabling, are internally fuse protected 
with a miniature circuit breaker (7).

FIGHTER 410P  is  delivered  with  a  8  kW  immersion 
heater (1). It is started and stopped via the microproes-
sor card (34). If a failure occurs there is a temperature 
limiter (6) (thermal cut-out) that is stopping the immer-
sion heater. An immersion heater without a  tempera-
ture limiter is not allowed to be mounted.

The temperature limiters are accessible behind the top 
front cover and are positioned to the right of the pan-
el.
The temperature limiters are reset by firmly pressing 
in its buttons.
The  temperature  limiter  may  only  be  reset  under  the 
supervision of a qualified installer.

Resetting  

the temperature limiter

Max current

Immersion heater

Art.nr.  611603

2

1

bar

3

0

4

2

1

bar

3

0

4

2

1

bar

3

0

4

Transparent, blåfärgad film (ej hål).

18,6

98,1             

26,3

4,2

86,3

92,7

126,8

129,8

132,8

145,2

272,5

336

41

19,2

83

90.5

111

98,6

523

10,5

Ø 52,8

53,5

135,3

130,7

15

70,5

135,3

261,5

r=4,5

37

23

9

2 st Ø 4,5, transparent, ofärgad film (ej hål).

OBS! Endast halv cirkel (radie=11)

Slits på baksidan

De 8 grårastrerade ytorna (Ø22)
skall ej förses med häftämne.

49,5

84,4

85,7

186,3

196,8

42,5

67,5

57,25

52

 161

Ø 13

Ø 18,5

Ø 62

Hål 16 x 31

Hål 16 x 16

313,2

 2 st urstansninga , bredd=5 och r=2,5

NOTE! 

The electrical installation, wiring and 

any service work must be done in strict   

conformity to current regulations 

under the supervision of a qualified 

electrician.

Immersion 
heater

Compressor

  Immersion heater output  Max current 

Breaker 

 

(kW) 

(A) 

(A)

 

  6,0 

30,3 

32 

 

  8,0 

39,0 

40

Summary of Contents for FIGHTER 410P

Page 1: ...INSTALLATION AND MAINTENANCE INSTRUCTION FIGHTER 410P 230V MOS GB 0823 2 FIGHTER 410P 511379 L E K...

Page 2: ...LEK LEK 1 2 LEK LEK 1 3 4 5...

Page 3: ...trol system Heating curve offset 2 22 Heating curve offset 0 22 Heating curve offset 2 22 Setting with diagrams 22 Service Opening the front panel 23 Refrigerant system 23 Channel description 23 Deali...

Page 4: ...sure 16 bar Immersion heater R50 8000W 230 V Operating pressure tap water 6 bar Expansion vessel tap water charge pressure 3 5 bar Expansion vessel heating water charge pressure 0 5 bar Pressure reduc...

Page 5: ...valve where the pressure and temperature are further reduced The refrigerant has now completed its circulation and returns to the evaporator A frost protection damper precedes the supply air side s h...

Page 6: ...Upper visible part of the front panel Numerical display Art nr 611822 2 1 bar 3 0 4 2 1 bar 3 0 4 2 1 bar 3 0 4 41 19 2 83 90 5 111 98 6 523 15 70 5 135 3 Switch Pressure gauge Indicator lamps Extra...

Page 7: ...tandby mode to normal mode 1 the numerical display can remain dimmed for a brief period This can also occur at extremely low outdoor tem peratures Extra hot water Pressing the Extra hot water button r...

Page 8: ...1 bar 3 0 4 111 523 Front panel FIGHTER 410P For Home Owners 6 Lower hidden part of the front panel Indicator lamps Heating curve selection Operating mode Channel selection I H J G L Miniature circuit...

Page 9: ...always shows channel 1 When you have browsed through the channels channel 1 returns after a while Heating curve selection Use the Heating curve selection knob to set the automatic heating control syst...

Page 10: ...eratures have time to stabilise Readjustment of basic settings Cold weather conditions If the room temperature is low increase the heating curve selection setting by one step If the room temperature i...

Page 11: ...Assembly takes place in the reverse order Every third month a reminder for cleaning the filter is shown in the display as A 01 Note that the time will be set to zero by setting the switch to 0 Cleani...

Page 12: ...eck one valve at a time as follows Open the valve Check that water flows through the valve Close the valve The heating system may need to be refilled after checking the safety valve 52 see the section...

Page 13: ...nd the highest radiator is 5 metres see figure If the standard initial pressure in the pressure vessel is not high enough it can be increased by adding air via the valve in the expansion vessel The in...

Page 14: ...Discharge pipes from tundishes shall have av vertical section of pipe at least 300 mm long before any elbows or bends in the pipework See following picture General If the vertical distance 300 mm is...

Page 15: ...kapacitet Fl de Tillg ngligt tryck kPa Internt tryckfall i panna inklusive armatur Tillg nglig pumpkapacitet pannans interntryckfall fr ndraget kPa 4 l h P 5 6 3 2 wg 10 200 0 0 20 400 30 600 40 800 5...

Page 16: ...e supply air battery is connected in parallel with the radiator circuit and heats the house s supply air The addi tional output is determined according to the diagram The water flow through the supply...

Page 17: ...ould not be changed In position A reduced position a low exhaust air respective supply air flow should be obtained How low is determined in each specific case NOTE The exhaust air flow must never drop...

Page 18: ...rthed This is done by making a sound electrical connection to the four ventilation ducts using the four earthing cables supplied The cables must then be connected to the earthing studs on top of the t...

Page 19: ...nging the output Connection Power rating as set at the factory NOTE Reset the temperature limiter it may have tripped during transport NOTE The switch 8 must not be moved from 0 until the boiler has b...

Page 20: ...ion B normal White cable 099 Exhaust air fan position C forced NOTE The same outlet must never be used for both fans Setting the fan capacity black white black white black white Normally the immersion...

Page 21: ...effektvakt 14 Rundstyrning RS och effektvakt EV Brytande kontaktfunktion RS EV EV RS SKYDDSKLENSP NNING SELV 1 2 3 4 5 6 7 8 ROMF LER RUNDSTYRING B R ER A B UTEF LER A Rundstyring eller belastningsvak...

Page 22: ...en it is opened for the first time Vent the FIGHTER through the safety valve 52 Other heating systems are vented using their respective venting screws Keep topping up and venting until all air has bee...

Page 23: ...in valve 51 using an R15 1 2 hose coupling Remove the cover 80 from the valve Now screw on the hose cou pling and open valve 51 Open safety valve 52 to let air into the system Draining the heating sys...

Page 24: ...RVA 2 V RMEKURVA 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 30 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1514 13 12 11 10 8 7 6 5 4 3 2 1 40 C UTETEMPERATUR 10 0 10 5 5 30 40 50 6...

Page 25: ...ual value 03 Outside temperature Actual value 04 Evaporation temperature Actual value 05 Extract air temperature Actual value 06 Curve slope Heating curve selection 07 Offset Heating curve offset 08 T...

Page 26: ...ion of a qualified installer Wrong operating mode selected with button 25 Closed or throttled filler valve 46 on the water h e a t e r Low temperature or a lack of hot water Circuit or main MCB trippe...

Page 27: ...efrosting is a sign of clogged ventilation or dirty filters See the sec tion Maintenance routines Cleaning the air filter Indications on the display NOTE This fault state must not be repeatedly reset...

Page 28: ...the fan this may need cleaning Contact your installer Cleaning the fan Luftningsskruv 16 Luftningsskruv 16 LEK LEK G RU N DFOS Type UPS 25 60 130 P N 59526447 230V PC 0017NIB 50Hz IP 44 TF 110 Class H...

Page 29: ...ge 0 27 26 169 28 15 14 5 41 40 39 38 37 36 35 Re 1 Re 2 Re 3 Re 4 Re 5 Re 6 Re 7 29 230 V 12 V B1 C1 34 Brun Bl Svart VR1 C2 C3 F3 F1 F2 C4 L2 L1 5 2 1 3 4 P3 P1 P2 1 2 3 4 5 6 7 8 6 0 kW 1 Noll ble...

Page 30: ...465 93 92 90 91 Skyddsklensp nning 16 Elektrisk matning 25 Dockning 16 A B och C Se Anslutning i Komponentlista Inom punktmarkerat omr de kan r rdragning fr n golv ej ske 70 A free space of 500 mm is...

Page 31: ...v k v 2 1 bar 3 0 4 LEK FILTER FILTER 6 7 107 145 8 78 9 16 17 18 1 25 31 32 30 41 44 19 27 33 37 38 39 40 42 44 35 73 152 50 80 14 109 53 55 56 58 59 68 11 65 70 103 71 148 150 47 51 85 88 89 96 82...

Page 32: ...ssories LEK 10 3 107 67 10 3 107 67 8 2 54 28 57 29 72 22 Top cabinet 245 mm Part no 089 424 Top cabinet 345 mm Part no 089 426 Top cabinet 385 535 mm Part no 089 428 Top cabinet A top cabinet is avai...

Page 33: ...t air Filter type G2 64 Drawing magnet supply air damper 65 Drying filter with tank 66 Air filter supply air Filter type G2 67 Contactor step 2 68 Docking pipe For the Installer 31 Connection Setting...

Page 34: ...e installed 47 50 dBA Height excl foot 15 40 mm 2 095 mm Width 600 mm Weight 200 kg Volume double jacket 70 litres Supply voltage 230 V 1 phase N Rated output circulation pump 100 W Rated output suppl...

Page 35: ......

Page 36: ...LLEMSTAD NB Tel 0168 477722 Fax 0168 476998 E mail info nibenl nl www nibenl nl V lund Varmeteknik Filial af NIBE AB Brog rdsvej 7 6920 Videb k Tel 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk...

Reviews: