Electrical connection
FIGHTER 200P
For the Installer
14
N
LL
1
N
(1)
(3)
(2)
The room thermostat (accessory) which must be
designed for 230 V has to be connected on terminal
(9) in position "Pil in" and "Pil ut". Position "N" on the
same terminal must be used, if the used thermostat
requires firm earthed neutral.
Make sure that the switch (18) is set to position "Auto".
A connection to earthed neutral is normally not requi-
red, however, it will result in faster regulations.
Connecting the room thermostat
Room thermostat
(RT 10)
9
Install the room thermostat in a neutral position where
the set temperature is required. A suitable place is on
a free inner wall in a hall approx. 1.5 m above the
floor. However, the sensor must not be prevented
from measuring the correct indoor temperature, e.g.
by placing in a niche, between shelves, behind a cur-
tain, above or close to a heat source or the like. Also
consider any draughts from exterior doors. Neither
must the unit be affected by solar incident radiation.
Mounting the room thermostat
The numerals refer to the connection notation in the
RT 10. Using another room thermostat the above
numerals will not be valid.