Control
13
For the Installer
FIGHTER 1210
Settings
NOTE!
Enter the chosen settings in the table on
page 2 of this manual.
The information is important for
future servicing.
18
18b
It is important with some concrete floors to maintain
the right floor temperature during an initial period. This
is so the floor dries correctly.
FIGHTER 1210 has a function for this drying process.
The process can be divided into two periods where
the number of days and temperature are set for
respective periods. This setting is made on the chan-
nel 18. When the FDP interval 1 is set to 0 days the
function is not active.
FDP int 1
Shows the number of days at step 1.
WW-out
Shows the flow temperature at step 1.
FDP int 2
Shows the number of days at step 2.
WW-out
Shows the flow temperature at step 2.
It is possible to set the number of days from 1 to 10
and the temperature from 15 to 50 °C. Once the dry-
ing process is finished the FIGHTER 1210 automati-
cally returns to normal control.
If a power failure occurs during the drying process the
current time and temperature are stored. When the
power returns the drying process continues with the
settings that applied before the power failure. Thus
the drying process is carried out to a 100%.
To return to display 9, press the Channel button. You
then return to the original display 1. Press the Channel
button and keep it held down for about 7 seconds to
return to service mode, display 9.
FDP-int1
8d
WW-out
25 °C
FDP-int2
8d
WW-out
40 °C