Control
FIGHTER 1210
For Home Owners
8
Brine In
Temperature of the incoming brine.
Brine Out
Temperature of the outgoing brine.
[P]
(Minimum permitted temperature for the brine
return from the heat pump).
This setting should only be changed by a special-
ist. It is used for minimum limiting with alarm, for
example as an anti-freezing function in ground-
water systems or exhaust air systems.
A suitable setting with an intermediate heat
exchanger would be 0 °C. When the lowest value
(-12) is set, minimum limiting and the alarm are
disabled.
Setting range: -12 - +10 °C.
WW-in
Current temperature of incoming heating medi-
um.
[P]
(Max permitted return temperature.)
Setting range: 40 – 55°C and A.
Setting WW-in
Maximum permitted return temperature for com-
pressor operation. To change, press the
Increase button once. A cursor will appear under
the figure for
WW-in. Press the Increase or Reduce button to
obtain the required value. If the value A is select-
ed, (automatic indirect control of the return tem-
perature) the operating pressure switch will indi-
rectly limit the return temperature. Press the
Channel button to continue.
HW start
The current temperature at the bottom part of the
water heater’s outer shell.
[P]
(Chosen start level for hot water production.)
Setting range: 30 - 49 °C.
Setting HW start
Press the Channel button. A cursor then appears
within the brackets for HW start. Press the
Increase or Reduce button to select the start
temperature for the hot water heating.
Press the Channel button to continue.
Outdoor
Current outdoor temperature.
Room
Current room temperature. Only shown if a room
sensor is fitted.
[P]
(The set Set point value on the room sensor.)
Setting range: 5 - 30 °C.
In normal mode, the above information appears on the
LCD-display of the heat pump.
WW-out
Current flow temperature
(Calculated flow temperature.)
Hot-water
Indication of the hot water temperature.
1
3
4
2
NOTE!
Enter the selected values on page 2 of
this Installation instruction. The
details are important for
service work.
FIGHTER 1210 has a two-line LCD display. The heat
pump can be set via this display and its associated
buttons.
Channel selection
The Channel button lets you browse through the
following display modes to find the information
you require.
Values within brackets are also described within
brackets.
If a value is programmable, this is denoted by a
[P]
(
Programmable
) in front of the value.
If the next value cannot be changed, you can access
the next menu by pressing Channel.
Setting
The first step when changing a value is to press
the Increase button once. A cursor (line) then
appears under the value. The value can then be
increased or reduced using the Increase or
Reduce buttons.
Available information and on-display settings
WW-in
37(53) °C
HW start 49(44) °C
WW-out
47(52) °C
Hot-water
48 °C
Outdoor
-14 °C
Room
20,5(20) °C
Brine In
+3 °C
Brine O
0(-12) °C