9.
Install the humidity sensor (BM20) and the insulation
plug in the right-hand space.
There is a cable tie on the sensor, indicating how
far in the sensor has to be positioned.
10.
Dismantle the grating.
11.
Install the insulation plug and sensor (BT21) furthest
in the left-hand section.
12.
Refit the grating.
13.
Switch the filters around. Filter ePM1 55% must be
placed on the supply air side.
14.
Fit the filter cassettes.
15.
Mark the change to the air flows on the duct connec-
tion plate (PZ4) on the upper side of the product.
Caution
In order to complete the conversion, changes
are required in menu 7.2.11.
NIBE ERS S40-350
Chapter 2 | Delivery and handling