Activating EMK 500
Activation of EMK 500 occurs the first time that a flow
is measured. Energy measurement is displayed in the
service information for your main unit.
For main products with software version 6869 or later,
check that the correct flow sensor is selected by going
to the menu 5.3.20 - “flow sensor”. Select EMK 500 if it
is not preset.
When EMK 500 is activated, it is shown in menu 3.1 -
“service info” and the menu with the registered values
is now available.
Caution
The example images are taken from VVM 500,
there may differences in the actual installation.
service info 3.1
config EB15
inc. power
int. add
heat med. pump
charge pump
display type
flow sensor
0
3x400 V
9 kW
Wilo Yonos Para 7.5
Wilo Yonos Para 7.5
EMK500
Supply temperature sensor
service info 3.1
climate system 1
heat meter
heating, compr. only.
hotwater, compr. only.
pool, compr. only.
cooling, compr. only.
heating, int. add. incl.
hw, incl. int. add
BF1
EB15
12.4 l/min
2 kWh
0 kWh
0 kWh
0 kWh
2 kWh
0 kWh
Technical specifications
EMK 500
9,0 – 150
l/min
Measurement range
0,1 – 27,0
kPa
Pressure drop
-15 – +85
°C
Ambient temperature
<125
°C
Medium temperature
28
(Ø mm)
Pipe connections
5 ±5%
VDC
Supply
0,1 - 4,75
V
Signal
067 178
Part No.
EMK 500 | GB