Docking, gas boiler
When docking a gas boiler to the heat pump it must be
ensured that the incoming water temperature from the
gas boiler to the heat pump does not exceed 60 °C.
Set the gas boiler thermostat to 60 °C. It is also important
that the charge flow does not exceed 800 l/h otherwise
this, as well as the high temperature, can affect the heat
pump operation negatively.
The immersion heater control in the heat pump must in-
stead control the circulation pump in the gas boiler. This
means that the symbol for the immersion heater is shown
in the display when there is a need for additional output.
-EB100
-AA5
-EM1