Docking oil boiler
When docking an oil boiler to the heat pump it must be
ensured that the incoming water temperature from the
oil boiler to the heat pump does not exceed 60 °C.
This is most appropriately achieved by installing temper-
ature limiting equipment "Laddomat type N". which is
part of docking kit DEH40. It is also important that the
charge flow does not exceed 800 l/h otherwise this, as
well as the high temperature, can affect the heat pump
operation negatively.
The immersion heater control in the heat pump must in-
stead control the circulation pump between the oil boiler
and the heat pump. This means that the symbol for the
immersion heater is shown in the display when there is
a need for additional output.