Nibe Contura Ci60 Installation Instructions Manual Download Page 15

!

GB

95

Service

Make sure it is possible to access the damper control and 
counterweight through hatches or ventilation grilles in the surround. 

RECESSING THE INSERT

Convection air

Sealing

The recess must not go all the way up to the ceiling. Leave an air 
gap of at least 20 mm closest to the ceiling. The recess must be 
sealed off above the convection exhaust. The seal must be a 50 
mm non-combustible material (see material requirements above) 

and must be placed no more than 100 mm above the upper edge of 
the convection exhaust. Use heat-resistant silicone, or a suitable 
equivalent, between the seal and chimney.  

The building material must not be combustible.
The thermal conductivity coefficient 

λ

 must be maximum

0.14 W/mK.
The building material must always be at least 50 mm thick.
Where the insulation properties of building material are given as a 
U-value, it must be maximum 1.4 W/ m²K.

Material requirements

The convection air ventilates the surround, cools the insert and 
carries hot air out into the room. The effective cross-section area 
on the air intake and exhaust must not be less than the stated 
values. The air intake must be positioned somewhere between 
floor level and the bottom of the insert, at the front or on the 
sides of the recess. The air exhaust must be positioned above the 
highest point of the insert at the front or the sides of the recess.

If the air intakes or exhausts are positioned on the sides, the 
areas for the left and right side respectively must be the same size 
to ensure that the insert is evenly cooled.
The distance between the exhausts on the sides and a combustible 
wall behind should be at least 100 mm.
Observe the minimum distance up to the ceiling (see the diagram 
on page 95).

Convection air in: 300 cm²
Convection air out: 300 cm²

When recessing the insert, adjacent walls that are not classed as 
fire walls or are considered unsuitable for exposure to heat must 
be protected by non-combustible building material in accordance 
with the specifications below.
All joints on the non-combustible material must be sealed using 
the method indicated by the manufacturer. The space between 
the insert and the recess must be ventilated in accordance with 
specifications/dimensions diagrams on page 97.

When connecting a steel flue, please refer to the particular 
manufacturer’s installation instructions. Observe the 
requirements for safe distances from the steel flue to combustible 
materials. Because of the strong heat radiating from the door, 
combustible materials must be placed a minimum of 1 m from 
the door. The insert must be installed with clearance to the 
building material, not in direct contact with it, to allow for thermal 
expansion of the insert.
Note that the area below and in front of the insert must comply 
with building regulations. See section “Hearth plate”.

Recessing the insert

List of suitable materials:
Aerated concrete  

λ 

= 0.12-0.14

Vermiculite  

λ 

= 0.12-0.14

Calcium silicate  

λ 

= 0.09

Summary of Contents for Contura Ci60

Page 1: ...Ci60 contura eu Installation instructions ...

Page 2: ...performance and issued test report no RRF 29 19 5301 The undersigned is responsible for the manufacture and conformity with the declared performance Niklas Gunnarsson Business area manager NIBE STOVES Markaryd June 24 2019 DECLARED PERFORMANCE Essential characteristics Performance Harmonised technical specification Reaction to fire NPD Minimum distance to combustible material Rear 100 mm Side 500 ...

Page 3: ...a qualified inspector Your local chimney sweep must also be informed of the installation as this will affect the routines for regular chimney sweeping services A warm welcome to Contura Welcome to the Contura family We hope you will get a great deal of pleasure from your new insert Congratulations on your purchase of a Contura insert You have acquired a reliable quality product with a timeless des...

Page 4: ...on how to install the Contura i60 We recommend the insert be installed by a qualified tradesperson to ensure it functions safely and properly Our Contura dealers can recommend suitable installers Dealer information is available at www contura eu An instruction manual on how to obtain optimal performance from your insert is also provided Please read this carefully and keep for future reference Stru...

Page 5: ...0 1530 1220 490 GB 85 Opening a side glass panel Prior to installation IMPORTANT DIMENSIONS PRIOR TO INSTALLATION Important dimensions 235 565 985 475 500 315 270 Air inlet Ø100 110 Height adjustment 130 lead in floor ...

Page 6: ...x3 GB 86 PRIOR TO INSTALLATION ...

Page 7: ...10 mm GB 87 PRIOR TO INSTALLATION ...

Page 8: ...the performance of the insert as follows Use the adjustable feet to level the insert Check that the door can be opened and closed Check that the damper knob can be moved back and forth to the max and min marks Performance check PRIOR TO INSTALLATION ...

Page 9: ...2 1 2 1 1 2 3 GB 89 PRIOR TO INSTALLATION Installing the metal ba e plates ...

Page 10: ...1 2 3 4 GB 90 Removing the hearth cladding PRIOR TO INSTALLATION ...

Page 11: ...5 6 7 GB 91 PRIOR TO INSTALLATION ...

Page 12: ...GB 92 Option Installing Powerstone OPTION ...

Page 13: ...The connection sleeve on the stove has an external diameter of Ø100 mm In warm spaces the duct should be insulated to prevent condensation using 30 mm mineral wool covered with a vapour barrier aluminium tape It is important that the lead in between the pipe and the wall or floor is sealed using jointing compound A 1 metre combustion air tube insulated to prevent condensation is available as an op...

Page 14: ...himney of at least 12 Pa The draft is affected primarily by the length and area of the chimney and also by how well sealed it is The minimum recommended chimney length is 3 5 m and a suitable cross section area is 150 200 cm2 Ø140 160 mm Carefully check that the chimney is sealed and that there is no leakage of smoke from the soot doors or connections Note that sharp bends and horizontal lengths i...

Page 15: ...If the air intakes or exhausts are positioned on the sides the areas for the left and right side respectively must be the same size to ensure that the insert is evenly cooled The distance between the exhausts on the sides and a combustible wall behind should be at least 100 mm Observe the minimum distance up to the ceiling see the diagram on page 95 Convection air in 300 cm Convection air out 300 ...

Page 16: ... upper edges see diagram to the right Wall made of non combustible material that is not in contact with combustible material and therefore has no minimum thickness requirement Unless otherwise stated these are the minimum dimensions Final inspection of the installation It is extremely important that the installation is inspected by an authorised inspection body before the stove is used You should ...

Page 17: ...n 300 cm2 Area in min 300 cm2 Heat shield Luftspalt GB 97 Area int min 300 cm2 20 mm Air gap 20 mm Air gap 20 mm Air gap 20 mm Air gap Area int min 300 cm2 Area int min 300 cm2 Area int min 300 cm2 min 100 min 460 min 460 Max 100 Max 100 Area ext min 300 cm2 Area ext min 300 cm2 Area ext min 300 cm2 Area ext min 300 cm2 Sealing Sealing Can be excluded if the chimney breast behind is approved and f...

Page 18: ......

Page 19: ......

Page 20: ...60 0 2019 07 09 NIBE AB Box 134 285 23 Markaryd Sweden contura eu Contura reserves the right to change dimensions and procedures specified in these instructions without prior notice Access the latest version at contura eu ...

Reviews: