The minimum distance in front of
the stove opening to combustible
parts of the building or interior
decoration must be at least 1,4 m.
The dimension diagrams only
show the minimum permitted
installation distances for the
stove. When connecting to a steel
flue, also note the safety distance
requirements of the flue. The
safety distance between an un-
insulated flue and a combustible
part of the building should be at
least 450 mm.
Installation distances
A = height from floor to chimney
connection upwards
B = height from floor to c/c chimney
connection rear
C = height from floor to air inlet
D = height from floor to lower edge
of hatch
E = height from floor to lower edge
of heat deflector
* If the stove is placed on a hearth plate made of glass for example (accessory), the height from the floor is affected by a distance corresponding to the thickness of the hearth plate, for a free standing
glass hearth plate this is 10 mm.
** To prevent discolouration of painted non-flammable walls we recommend that the same side distance as to combustible walls is used.
INSTALLATION AGAINST COMBUSTIBLE WALLS
INSTALLATION AGAINST FIREWALLS
C310
850
750
375
2100
D 345
E 310
85
200
Combustible roof
A 795
B 700
C 350
65
45
80
30
375
140
Air inlet Ø65
Ø150
190
50
475
1200
100**
Fire-retardant wall of
brick or concrete
240
100
875
100
500
Combustible wall