8
COMPACT-SOL
GB
1 Terminal block
2
Isolator switch
5
Thermostat/temperature limiter.
The thermostat is adjustable between
60 – 80 °C.
6
Immersion heater
Assembly
Unscrew the water heater from the wooden pallet. The
water heater can be raised by screwing out the length
of the feet.
Instalation
Filling
1 Check that the safety/drainage valve (23) is
closed.
2 Open the shut-off valve (22).
3 Release air from the water heater by opening a
hot water tap. When only water comes out of
the tap this can be closed.
Switch the current off with the isolator switch (2).
Electrical installation
The water heater is equipped with an isolator switch (2).
Connect the supply via plinth (1).
In a 1-phase installation the water heater gives 1 kW
and a 2 phase installation gives 3 kW.
The water heater must be filled with water
before the power is switched on.
NOTE!
5
6
2
1
A
B
3 kW
230 V~
1-fas
L1
N
PE
1
400 V~
2-fas
L1
L2
PE
1
5
6
Läge 3 kW
Läge 6 kW
2
400 V~
3-fas
11
21
31
12
22
32
P3
P1
P2
5
2
4
P3
P1
P2
5
2
4
P3
P1
P2
5
2
4
L3
L2
L1
PE
6 kW
2
P3
P1
P2
5
2
4
L1
L2
L3
L1
L2
L3
Electrical circuit diagram
Electrical installation and any
servicing must be done under the super
vision of a qualified electrician
NOTE!
Instalation
Pipe installation
The water heater is only designed for upright installa-
tion.
The valve connector must not be used for external instal-
lation, relocation or separation.
All connections are equipped with compression ring
couplings for copper or plastic pipes. Internal support
bushes should be fitted when a plastic pipe or annealed
copper pipe is used. The mixer valve (25) is set for the
desired hot water temperature. Turn the mixer knob
anticlockwise to increase hot water temperature. Setting
range 40–65°C.
The solar panel's charge automatic device must be lim-
ited to a max temperature of 90 °C. This is to prevent
temperatures higher than 95 °C in the water heater.
An overflow pipe should be routed from the safety valve
to an appropriate drain. The size of the overflow pipe
must be the same as on the safety valve (Ø 15 mm). The
overflow pipe must be routed downwards to prevent
water pockets and to be frost proof. The outlet of the
overflow pipe must be visible.
Thermostat
On delivery, the heater's thermostat is set to a hot water
temperature of approx. 60 °C, if another temperature is
required, set it using the thermostat knob (7).