Installation and Operation Manual
Radiant Heat Panel
11
RHP-1&2 0511
Use 3/4” PEX or 3/4” copper (use 1” on RHP-2) to connect from the RHP panel
to the manifolds and from the panel to the heat source (page 9).
Panel connections consist of a union nut, washer, and a FPT adapter. These
components must be used on every installation. System connections will consist of
a 3/4” MPT x PEX adapter or 3/4” MPT x copper adapter, depending on the
material used (the adapters will be 1” on RHP-2).
Follow these steps and refer to picture below.
Screw 3/4” FIP adapter (D)(supplied with panel) into adapter (E) or (H) using appropriate
thread sealant.
Without disturbing gasket (C) place assembly against flanged steel pipe (A)
Slide nut (B) over adapter (D) and finger tighten.
Use 2, 30mm or adjustable wrenches. Attach 1 to adapter (D) and hold it firmly in place.
Attach other wrench to union nut (B) and tighten 1/4 turn.
Pipe Connections
Step 1
Step 2
Step 3
Step 4
A - Flanged pipe on panel
B - Nut on panel
C - Rubber gasket
D - 3/4” FIP adapter
E - PEX x Male thread adapter
F - Copper crimp ring (SS clamp or SS sleeve)
G - 3/4” PEX
Installation Instructions
Summary of Contents for RHP-1
Page 17: ...Installation and Operation Manual Radiant Heat Panel 17 RHP 1 2 0511 ...
Page 20: ...Installation and Operation Manual Radiant Heat Panel 20 RHP 1 2 0511 ...
Page 21: ...Installation and Operation Manual Radiant Heat Panel 21 RHP 1 2 0511 ...
Page 22: ...Installation and Operation Manual Radiant Heat Panel 22 RHP 1 2 0511 ...
Page 23: ...Installation and Operation Manual Radiant Heat Panel 23 RHP 1 2 0511 ...
Page 24: ...Installation and Operation Manual Radiant Heat Panel 24 RHP 1 2 0511 ...
Page 25: ...Installation and Operation Manual Radiant Heat Panel 25 RHP 1 2 0511 ...
Page 26: ...Installation and Operation Manual Radiant Heat Panel 26 RHP 1 2 0511 ...
Page 27: ...Installation and Operation Manual Radiant Heat Panel 27 RHP 1 2 0511 ...
Page 28: ...Installation and Operation Manual Radiant Heat Panel 28 RHP 1 2 0511 ...