![Niagara Tridium T-600 Mounting Manual Download Page 14](http://html.mh-extra.com/html/niagara/tridium-t-600/tridium-t-600_mounting-manual_1685748014.webp)
Network Controller 6 Mounting and Wiring Guide
Updated: January 16, 2012
Wiring Details
Communications Wiring
14
WPM-
XXX
All models of wall power modules (US, EUR, UK, JA) are self-contained, isolated, switching power supplies
designed to plug into a standard building power receptacle of appropriate voltage. To supply power to the T-600,
you then simply plug the barrel connector plug from the WPM-
XXX
into the barrel power connector on the
Caution
Do not plug the barrel connector plug from the WPM-
XXX
into the T-600 until all other mounting
“Power Up and Initial Checkout,”
Communications Wiring
Connect communications wiring to the T-600 using ports on the bottom of the unit (
), which include:
•
•
Note
Prior to connecting cables, provide strain relief for them to prevent damage to the controller.
Figure 6
T-600 controller bottom side (cover removed).
Ethernet
Two, female 10/100-Mbit Ethernet connections are provided on the T-600. These are RJ-45 connectors labeled
LAN2 and LAN1. Use a standard Ethernet patch cable for connecting to a hub or Ethernet switch. An activity
LED for each Ethernet port is visible, and are labeled “LAN2” and “LAN1” on the cover.
The factory-default IP address for
LAN1
on a T-600 is
192.168.1.12
n
, where the last numeral
n
in the
address matches the T-600’s serial number, and subnet mask is
255.255.255.0
. By default, LAN2 on a T-600
is disabled. Refer to the
JACE NiagaraAX Install and Startup Guide
for details on changing IP address.
Note
Typically, you
only use LAN1
(primary port), unless you have a specific application for isolating a
driver’s network traffic to a separate LAN, using LAN2. Do
not
use LAN2 as the primary port.
NiMH
Battery
Connector
20 Pin
Connector
(I/O and Power
Modules)
Earth Ground
Spade Lug
s + –
port (future use)
Battery in bracket
(on top of option
cards, if any)
Primary
(RJ-45)
LAN 1
Ethernet (RJ-45)
LAN 2
Option Slot area
(Slot #1 this side)
Barrel power
connector for
(3-pos.)
COM2
(DB-9)
COM1