background image

Physical Characteristics

Dimensions and Weight

Dimensions

Width

303.3 mm (11.94 in.)

Depth

463.6 mm (18.25 in.)

Height

177.1 mm (6.97 in.)

Weight (empty chassis with power supply installed)

11.7 kg (25.7 lbs)

DC Power Supply Field Wiring Specifications

Notice

 

Use only copper wire. For use in class 1 circuits only.

Note

 

Refer to the 

Data Record System AD User Manual

 for the power supply connection requirements.

Gauge

2.5 mm

2

 to 16 mm

2

 (14 AWG to 6 AWG) conductor

Wire strip length

12 mm

Temperature rating

60 °C minimum

Wires per terminal

1

Torque for screw terminals

1.7 to 1.8 N · m (15 to 15.9 lb · in.)

Single ferrule

Barrel length

12 mm (0.47 in.)

Maximum cross section of conductor plus ferrule

16 mm

2

 (6 AWG)

Recommended crimping tool

Crimpfox 16 S crimping tool

Connector securement

Securement type

Screw locking

Torque for screw flanges

0.3 N · m (2.7 lb · in.)

Protective Earthing

When using the product with hazardous voltage PXIe modules or I/O (>30 VAC, 42.4 V

pk

, 60 VDC), connect the product to the protective earth terminal

before connecting to DC power.

Notice

 

The facility installation shall provide a means for connection to protective earth, and qualified personnel shall install a protective earthing

conductor from the protective earthing terminal on the product to the protective earth wire in the facility.

Notice

 

Use only copper wire to connect the protective earthing terminal of your product to the protective earth wire in the facility.

Protective Earth Terminal Wiring

Grounding wire gauge

2.1 mm

2

 (14 AWG)

Ring lug

# 8

Protective earth terminal torque

1.13 N · m (10 lb · in.)

Export Compliance

This product is subject to control under the U.S. Export Administration Regulations (15 CFR Part 730 et. seq.) administered by the U.S. Department of

Commerce's Bureau of Industry and Security (BIS) (

www.bis.doc.gov

) and other applicable U.S. export control laws and sanctions regulations. This product

may also be subject to additional license requirements of other countries' regulations.

Additionally, this product may also require export licensing before being returned to NI. The issuance of a Return Material Authorization (RMA) by NI does

not constitute export authorization. The user must comply with all applicable export laws prior to exporting or re-exporting this product. See 

ni.com/legal/

export-compliance

 for more information and to request relevant import classification codes (e.g. HTS), export classification codes (e.g. ECCN), and other

import/export data.

Environmental Management

NI is committed to designing and manufacturing products in an environmentally responsible manner. NI recognizes that eliminating certain hazardous

substances from our products is beneficial to the environment and to NI customers.

For additional environmental information, refer to the 

Commitment to the Environment

 web page at 

ni.com/environment

. This page contains the environmental

regulations and directives with which NI complies, as well as other environmental information not included in this document.

4

  | 

ni.com

  | 

PXIe-1092DC Safety, Environmental, and Regulatory Information

Reviews: