Isolation and Safety Guidelines

Caution

Read the following information before 

attempting to connect any circuits which may contain 
hazardous voltages to the FP-DO-400.

This section describes the isolation of the FP-DO-400 and its 
compliance with international safety standards. The outputs are 
isolated from the backplane provided by the terminal base with an 
optical isolation barrier designed and tested to provide protection 
against fault voltages of up to 3000 Vrms. In addition, the 
FP-DO-400 provides double insulation (compliant to UL and 
IEC safety standards) for working common mode voltages of 
250 Vrms. Safety standards (such as those published by UL and 
IEC) require the use of double insulation between hazardous 
voltages and any human-accessible parts or circuits. You should 
never attempt to use any isolation product between human 
accessible parts (such as DIN rails or monitoring stations) and 
circuits which may be at hazardous potentials under normal 
conditions, unless the product is specifically designed (as the 
FP-DO-400 is) for such an application.

Even when a product like the FP-DO-400 is used in applications 
with hazardous potentials, follow these guidelines to ensure a safe 
total system.

The safety isolation of the FP-DO-400 is from input to output, 
not between channels on the same module. If any of the 
channels on a module are wired at a hazardous potential, 
ensure that all other devices or circuits connected to that 
module are properly insulated from human contact.

Do not share the external supply voltages (V and C on the 
terminal base) with other devices (including other FieldPoint 
devices) unless those devices are also isolated from human 
contact.

As with any hazardous voltage wiring, ensure that all wiring 
and connections meet with applicable electrical codes or 
common sense practices. Mount terminal bases in an area, 
position, or cabinet that prevents accidental or unauthorized 
access to wiring with hazardous voltages.

The isolation of the FP-DO-400 is certified as double insulated 
for normal operating voltages of 250 Vrms. Do not use the 
FP-DO-400 as the sole isolating barrier between human 
contact and working voltages of more than 250 Vrms.

Summary of Contents for FieldPoint FP-DO-400

Page 1: ...r FieldPoint network module you are using with the FP DO 400 Features The FP DO 400 is a FieldPoint discrete output module with the following features Eight discrete output channels Sourcing outputs supply 2 A per channel 9 A2 per module Compatible with voltages from 5 to 30 VDC On Off LED indicators Hot plug and play operation 3 000 V input to output isolation Double insulated for 250 V safe work...

Page 2: ...eld devices Although the external supply is not needed for the internal operation of the FP DO 400 the outputs source current from this external supply You may connect an external supply to power field devices by connecting to the V and C terminals of the terminal base Each channel has one output terminal Vout a common terminal COM internally connected to the C terminal and a supply terminal Vsup ...

Page 3: ...nals of each channel Table 1 Terminal Assignments Channel Terminal Numbers Vout Vsup COM 0 1 17 2 18 1 3 19 4 20 2 5 21 6 22 3 7 23 8 24 4 9 25 10 26 5 11 27 12 28 6 13 29 14 30 7 15 31 16 32 C V Vout COM a Total Current Less Than 5 Amps Load Vout COM Load C V Vout COM b Total Current Greater Than 5 Amps Load Vout Vsup Vsup COM COM COM Load ...

Page 4: ...er The result must be equal to or less than 9 A2 For example two channels with 2 A and one channel with 1 A 9 Α2 would be as follows 2 A 2 2 A 2 1 A 2 9 Α2 The outputs must not be short circuited to the potential of the C or COM terminals the negative voltage of the external supply Such a short circuit would cause many amps of current to flow through an output and would damage the output Check all...

Page 5: ...d into a terminal base and power is applied the green POWER indicator turns on and the FP DO 400 informs the network module of its presence When the network module recognizes the FP DO 400 it sends initial configuration information to the FP DO 400 After receiving this initial information the green READY indicator turns on and the FP DO 400 is in its normal operating mode In addition to the green ...

Page 6: ...s unless the product is specifically designed as the FP DO 400 is for such an application Even when a product like the FP DO 400 is used in applications with hazardous potentials follow these guidelines to ensure a safe total system The safety isolation of the FP DO 400 is from input to output not between channels on the same module If any of the channels on a module are wired at a hazardous poten...

Page 7: ... 9 A2 For example 1 A on all eight channels or 2 A on two channels 5 V Voltage Range Output impedance 2 Ohms Maximum output current 0 67 A per channel 1 35 A2 per module Note Sum of output currents squared must be less than 1 35 A2 For example 0 4 A on all eight channels or 0 67 A on three channels Output delay times 50 µs Isolation 3 000 Vrms Safety isolation working voltage 250 Vrms designed per...

Page 8: ...solation EN 61010 double insulation for 250 Vrms working isolation installation category II EMC directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 meters Mechanical Dimensions Figure 5 shows the mechanical dimensions of the FP DO 400 installed onto a terminal base Dimensions are given in inches millimeters Figure 5 Mechanical Dimensions 4 31 109 5 3 60 91 44 4 22 107 ...

Reviews: