nextys OR20 Instruction Manual Download Page 3

OR20

Instruction Manual

OR20 V4.0

www.nextys.com

Page 3/5

USER INSTRUCTIONS

1) Description:

DIN rail Universal Active Oring Controller for redundant connection to a common Load of 2 DC Power supplies of same rating, with any voltage in the range

12…85Vdc and Load Current ≤ 20A.

Warning:

 voltages ≥ 60Vdc are dangerous! Use appropriate safety rules!

2) Installation:

use DIN-rails according to EN 60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where

the device is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).

3) Connections

: the device is equipped with pluggable screw terminals. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input

power and waited for internal capacitors discharge (minimum 1 minute)

In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of:

60°C for ambient up to 45°C

75°C for ambient up to 60°C

90°C for ambient up to 70°C

Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5)

4) Input/Output connection:

 The device is suitable for

SELV

 and

PELV

 circuitry (if you use a source that having Uout higher 60Vdc is not a SELV device)

Check Uout before connecting the power supply to the load.

5) Operating:

at the OR20 is possible connect 2 DC Power supplies in order to obtain a redundancy connection system (see Fig.7), the 2 Power supplies must have setted the

same Output voltage rating in order to ensure the corrected redundancy. The correctly current sharing is possible verify through the status LEDs “IN1 OK” and “IN2 OK” (see

Fig.1), when you connect 2 DC Power supplies, what is has the higher output voltage determines the voltage threshold and turns on the respective LED, in order to ensure the

correct current sharing now you must increase Output voltage of the other Power supply until the two LEDs will not be turned on simultaneously. The precision of redundancy

which allows the simultaneous lighting of the two LEDs is about 10% of the highest voltage threshold. When the two LEDs are simultaneously turned on is ensured the

redundancy and also the Diagnostic Output "OR OK" relay it is closed.

Fig.1

Connections

Fig.2

Dimensions

Fig.3

Distances

(1)

Input PS1 20A Max.

(2)

Input PS2 20A Max.

(3)

Output Load 20A Max.

(4)

Diagnostic Output

(dry contact, NC output OK)

(5)

Green LED: IN1 OK

(6)

Green LED: IN2 OK

Input DC Line:

IN1 + = Positive DC

IN1 - = Negative DC

IN2 + = Positive DC

IN2 - = Negative DC

Output DC Line:

OUT + = Positive DC

OUT - = Negative DC

Dimension

W

D

H

mm (inc)

35.0 (1.38)

104.0 (4.09)

103.0 (4.05)

Distance

A

B

mm (inc)

20 (0.8)

20 (0.8)

3

OR20_1680-21539-0007-E-1117

Summary of Contents for OR20

Page 1: ...5Vdc on a single model 20A Max Extremely low loss up to 99 efficiency Pluggable connectors Hot pluggable Up to 70 C operating temperature with no derating INDEX Page Installation Requirements 2 Declaration of Conformity 2 User Instructions 3 Connections 3 Dimensions 3 Distances 3 Mounting 4 Dismounting 4 Set up 5 Environment 5 Accessory Device 5 1 OR20_1680 21539 0007 E 1117 ...

Page 2: ...ischarge minimum 1 minute RISCHIO USTIONI ESPLOSIONE INCENDIO SCOSSA LESIONI GRAVI Non effettuare mai operazioni sulle parti sotto tensione Pericolo di lesioni letali Il contenitore può scottare lasciar quindi raffreddare il dispositivo prima di toccarlo Non far entrare liquidi o oggetti estranei nel dispositivo Per evitare scintille non collegare o scollegare l apparecchiatura prima di avere tolt...

Page 3: ...e is suitable for SELV and PELV circuitry if you use a source that having Uout higher 60Vdc is not a SELV device Check Uout before connecting the power supply to the load 5 Operating at the OR20 is possible connect 2 DC Power supplies in order to obtain a redundancy connection system see Fig 7 the 2 Power supplies must have setted the same Output voltage rating in order to ensure the corrected red...

Page 4: ...ified in the I S manual of each family Mounting 1 2 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hits the stop 4 Press against the bottom for locking 3 4 Dismounting 1 Pull down the slide clamp lever 2 Tilt the unit upward 3 Unhook the unit from the rail 1 2 3 Fig 5 Recommended connecting cable Recommended Tightening torque 0 5 0 6Nm ...

Page 5: ...n condensing No Derating Note Data may change without prior notice in order to improve the product Please refer to the latest version of the Instruction Manual for each product by visiting www nextys com See also the products below that can be used in conjunction with OR20 units This device can be used in conjunction with every each our power supply that is able to provide an regulated Uout includ...

Page 6: ... 87 65 osman coban pewatron com Pressure Sensors Load Cells Philipp Kistler Phone 41 44 877 35 03 philipp kistler pewatron com Power supplies Sebastiano Leggio Phone 41 44 877 35 06 sebastiano leggio pewatron com Accelerometers Sensor elements Christoph Kleye Phone 49 89 374 288 87 61 christoph kleye pewatron com Harald Thomas Phone 49 89 374 288 87 23 harald thomas pewatron com Sales Other Countr...

Reviews: