BATTERY, AUTO NOTIFICATION STATUS:

The display digits 6-10 represent the Battery
Status or indicates Auto Notification Status.

BATTERY STATUS:

‘XX.XX’ Battery voltage (Normal readings ‘12.40-13.20’)

‘Disc’ Battery disconnected

Displays when Battery is disconnected or Battery voltage is
below 1.5 volts

‘Rep_’ Check or Replace Battery

(The ‘_ ‘ indicates the reason for failure “numeric value”)

1 = Battery failed due to load test
2 = Battery failed due to charge cycling
3 = Battery failed initial load test
See (Battery Troubleshooting)

Auto Notification:
Notification will occur on Battery Disconnected or Battery
Replacement Errors.

AUTO NOTIFICATION STATUS:

"BUSY" - Notification System Lines Busy
"INUSE" - Phone line is In Use
"DIAL" - Dialing Notification System
"CONND" - Connected to Notification System
"INFOS" - Error Information sent
"NLINE" - No Phone Line Connected
"MFAIL" - Internal Notification System Problem

BATTERY TROUBLESHOOTING

If you are receiving a replace code on your NexPump dis-
play, do the following:
1. If you have Auto Notification, Disconnect the Phone Line
2. Disconnect the Battery, you DO NOT need to power off
the NexPump System Unit.
3. Check fluid levels (See BATTERY FLUID LOW Section
below)
4. If you DO NOT need to correct the fluid levels then you
should replace the Battery, Follow the section on Battery
Replacement
5. Re-Connect battery, Attach the battery cables to 

t

he battery -

the BLACK wire to the NEGATIVE(-) post, the RED wire to the
POSITIVE (+) post and tighten securely.

IMPORTANT: Check the ‘Battery Reverse’ LED on the
NexPump System Unit and if it is illuminated the connec-
tions are reversed.
6. Perform a Battery Reset. 
7. LCD will display ‘Battery Reset’.

8. Charging cycle will begin.
9. If ‘REP_’ code sounds again soon after this procedure replace the
Battery.

BATTERY MAINTENANCE:

Check Fluid levels, if applicable in Battery at least once
every 6 months.

BATTERY REPLACEMENT:

IMPORTANT:  Review the safety instructions before proceed-
ing.
1. Disconnect the Battery.
2. Remove old Battery and dispose of properly. 
3. Connect new Battery, Attach the battery cables to the battery -
the BLACK wire to the NEGATIVE(-) post, the RED wire to the
POSITIVE (+) post and tighten securely.
IMPORTANT: Check the ‘Battery Reverse’ LED on the
NexPump System Unit and if it is illuminated the connec-
tions are reversed.
4. Perform a Battery Reset. Function Button until ‘R’ displays (
5. LCD will display ‘Battery Reset’.
6. Charging cycle will begin.

BATTERY FLUID LOW: (LEAD-ACID BATTERY)

Follow the procedure below to refill the battery cells.
IMPORTANT: Follow the power off procedure and review the
safety instructions before proceeding.
Remove the cell caps of battery. Add distilled water to each
cell. If distilled water is not available tap water with a low
mineral content may be used. NEVER ADD MORE ACID. Fill
the battery cell so water is just below the fill cap.

BATTERY LIFE:

Battery life is approximately four years of the battery being in
service. Most Deep-Cycle Batteries can endure hundreds of dis-
charges and charges. The NexPump performs many tests to
check the life of the battery and should alert you of potential bat-
tery problems.

CLEANING BATTERY TERMINALS:

Remove the battery cables and clean the battery posts with a

battery post terminal cleaner or a wire brush. A 50/50 solution of
water and baking soda may also be used if necessary. Do not
allow the cleaning solution water to enter the battery. Thoroughly
dry the posts and apply petroleum jelly or another terminal protec-
tive material if needed. 

7

Summary of Contents for Ai2800

Page 1: ...hone 630 365 4NEX 4639 Fax 630 365 6919 Email support nexpump com Web Address www nexpump com Manual 3 01 0002 NexPump is a Registered Trademark of NexPump Inc Copyright 2003 2010 NexPump Inc All Righ...

Page 2: ...instructions for the NexPump Follow these important safety precautions Failure to follow safety precautions can result in personal injury or damage to the NexPump CAUTION To reduce the risk of injury...

Page 3: ...ause an explosion Remove personal metal items such as rings bracelets neck laces and or watches when working with a battery A battery can produce a short circuit current high enough to weld a ring or...

Page 4: ...e correct direction when installing the check valve Note If you are installing a single pump version install using Diagram A as a reference The second pump would be your installed electric pump PARTS...

Page 5: ...the mount ing bracket at the top Verify the sensor is not tilted in any way Step 2 SECURE WIRES Secure the pump and sensor wires to discharge pipes with nylon wire ties IMPORTANT Make sure the wire t...

Page 6: ...etup See Mode Selection NexPump Operation The NexPump will schedule an auto matic self test approximately two minutes after power up If there are any errors they will be displayed on the LCD display a...

Page 7: ...ode position on display o NexPump WILL display and sound an alarm if pump s are activated Indicated by A in the corresponding pump location Manual Mode Used to manually turn on both pumps o Switch in...

Page 8: ...tery Reset 8 Charging cycle will begin 9 If REP_ code sounds again soon after this procedure replace the Battery BATTERY MAINTENANCE Check Fluid levels if applicable in Battery at least once every 6 m...

Page 9: ...n and battery state before going to battery power will affect the calculated time throughout the power loss An alarm will also sound from the loss of electric power which may silenced See Silencing th...

Page 10: ...he pump is drawing to little current Troubleshooting H Clear alarm and run self test if pump again shows failure with H then pump is faulty Troubleshooting L Clear alarm and run self test if pump show...

Page 11: ...e last location of the display release the function button The display will show Alarm Cleared and return to normal PUMP REPLACEMENT Displayed as R or r Pump has reached average life span Pump may sti...

Page 12: ...electrical power cord The NexPump will remember what state the charge system was in and re enable the charging state to the condition is was when the unit was turned off After re con necting the batt...

Page 13: ...CING THE ALARM Repeat the above section on Silencing the alarm Instead of a S displaying a U will display DISABLING THE ALARM The alarm can be disabled if needed When disabled the alarm will not sound...

Page 14: ...s error is detected You may Disable the Alarm to stop the alarm sounding until the error is corrected Auto Notification Module Installed Notification will occur on a VRef Malfunctions Note VRef availa...

Page 15: ...lved Auto Notification Module Installed Notification will occur on an electric power loss If the alarm was silenced within 5 minutes of the alarm the notification system will be postponed If the alarm...

Page 16: ...ed again of the power failure Important Note Each time the alarm is cleared or after a call has been completed a notification counter is reset and will not allow the notification process to begin for...

Page 17: ...otification occurring after a silence period during a pro longed power outage Simply switch the mode to primary This will no longer sound the alarm or Notify on pump activa tion Remember to switch the...

Page 18: ...he Primary Mode for the duration of the event or if your main electric pump has failed 2 Sensor Alarms a High Water Alerts should NOT be cleared however the NexPump should be allowed to operate under...

Page 19: ...d Manual Test 1 Press Function Button Until T appears 6 seconds 2 Release Function Button 3 Test is scheduled Get Serial Number 1 The NexPumps serial number is located on the rear unit or proceed to s...

Page 20: ...d Page 12 ALDIS Alarm is disabled Resets in 5 days F Charge Status Page 11 Off Charge is off battery is fully charged Fxx Indicates the Full charge mode Txx Indicates the Trickle charge mode Mxx Indic...

Page 21: ...prepaid properly packed and insured NexPump Inc bears trans portation cost of the repaired product back to the purchaser This warranty applied only to the original purchaser NO OTHER WARRANTIES ARE E...

Page 22: ...21 Diagram A NexPump Ai5600 Installed as only pump Operating in Primary Mode...

Page 23: ...22 Diagram B NexPump Ai5600 Installed with existing pump Operating in Primary or Backup Mode Recommended Configuration...

Page 24: ...23 Diagram C NexPump Ai2800 Installed with existing pump Operating in Backup Mode ONLY...

Reviews: