CONNECTOR INSTALLATION ON THE CABLE
1
Thoroughly clean cable reducer and contact.
2
Lubricate* the cable reducer and inside surface of the connector.
3
Slide the connector housing on to the reducer until it cannot advance any further.
4
Insert the supplied hex key into the pin contact. Insert the threaded end of the pin contact into the mating part and
engage threads.
Take care not to cross threads.
5
Tighten with the supplied hex key until the key has taken a set.
NOTE:
-The hex key must be inserted in the pin contact until it cannot advance any further.
-The hex key is only usable twice (once every side).
cable reducer
lubricate
pin contact
hex key
clean thoroughly
* USE ONLY THE SILICONE LUBRICANT SUPPLIED
IS97082-ENG - 200LR/G