Nexans Euromold 200LR Installation Instructions Manual Download Page 1

•  For indoor and outdoor applications.

•  Only for cables NF C 33-226, UTE C 33-223, NF C 33-223 & HN 33-S-23 [Part 1], 

  NF C 33-220 (HN 33-S-22) with graphite coating screen [Part 2],

  NF C 33-220 (HN 33-S-22) with extruded semi-conductive screen [Part 3].

•  In case the ambient temperature is less then 0°C, it could be necessary to warm up the  

  sealing mastic and tape.

CAUTION : Read instructions thoroughly and completely prior to beginning installation.

Installation Instructions Separable Elbow Connector - CENELEC interface type A

(K)200LR

Up to 24 kV

Check if the diameter over cable core insulation is in accordance with 

the cable reducer range as indicated in table below:

Cable reducer size

(see marking inside cable reducer)

200CA-12

200CA-16

13.0

17.5

21.0

25.0

Dia. over core insulation (mm)

min

max

This product should be installed only by competent personnel trained in good safety practices involving 
high voltage electrical equipment. These instructions are not intended as a substitute for adequate 
training or experience in such safety practices. These instructions do not attempt to provide for every 
possible contingency. Failure to follow these instructions could result in damage to the product and 
serious or fatal injury. IMPORTANT : Cable and associated apparatus must be de-energised, locked 
out, and tagged prior to product installation.  

Page 1/9

IS97082-ENG - 200LR/G-MT345

15 January 2018 - Revision 0 

- Supersedes edition of 3 June 2016

IS97082-ENG - 200LR/G

-MT345 - Revision 0

Summary of Contents for Euromold 200LR

Page 1: ...ndicated in table below Cable reducer size see marking inside cable reducer 200CA 12 200CA 16 13 0 17 5 21 0 25 0 Dia over core insulation mm min max This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment These instructions are not intended as a substitute for adequate training or experience in such safety practices...

Page 2: ...Cable reducer 200CA Conductor contact 200LRF 200LRMC hex Contents Elbow connector housing 200LR G Roll adhesive tape Installation instructions Silicone grease wipers Gloves Bail restraint 200LRBA 3x Water sealing mastic type MWS IS97082 ENG 200LR G MT345 Revision 0 Page 2 9 ...

Page 3: ...the cable end a Slightly round off the edge of the core insulation z Remove the extruded conductive screen 4 Cut longitudinal split s in the outer sheath to a point 40 mm from the edge 5 Using a blunt tool make a slight funnel of the outer sheath to fit the earthing device underneath the sheath 6 Install the earthing device underneath the outer sheath protruding for a distance of max 20 mm 7 Cleat...

Page 4: ...r sealing mastic water sealing mastic adhesive tape solder block on the braid 5 two layers of semi conduc tive tape 5 WATERSEALING earthing device 1 As a protection wrap a few turns of adhesive tape around the conductor end 2 Lubricate the indicated area cable surface and inner surface of the reducer 3 Slide the reducer down the cable 4 Remove the protective adhesive tape from the conductor INSTAL...

Page 5: ...interface 2 Tighten the contact until the bolt head shears off For 70 95 mm tighten again until the second level of the bolt head shears off 3 After tightening the contact slide the cable reducer up until it butts against the contact Only for 70 95 mm hex SW 5 mm Page 5 9 IS97082 ENG 200LR G MT345 Revision 0 ...

Page 6: ... contact Insert the threaded end of the pin contact into the mating part and engage threads Take care not to cross threads 5 Tighten with the supplied hex key until the key has taken a set NOTE The hex key must be inserted in the pin contact until it cannot advance any further The hex key is only usable twice once every side cable reducer lubricate pin contact hex key clean thoroughly USE ONLY THE...

Page 7: ... as close as possible to the connector IMPORTANT NOTES Never disconnect the connector from energised equipment nor energise a disconnected connector without previously installing an appropriate mating part Do not allow hydrocarbon oils or solvents to contaminate the E P D M rubber In the event of contamination wipe the surface clean with a dry cloth 4 Connect earthing lead of the connector and fle...

Page 8: ...oid sharp edges 8 Apply 2 layers of semi conductive tape 50 stretch 50 overlap as follows start taping on the metal straps ensure the splits are covered up to a point 40 mm behind the outer sheath Without cutting the tape apply a second layer back to the start 9 Remove the core insulation from the conductor for a distance of 30 mm a Using an appropriate solvent thoroughly remove the graphite coati...

Page 9: ...derneath the outer sheath Have it protruded by maximum 20 mm 8 Cleat the outer sheath using the stainless steel straps Twist straps twice around the cable and fold back the ends to avoid sharp edges 9 Apply 1 layer of semi conductive tape 50 stretch 50 overlap on the metal straps ensure the splits are covered a Remove the core insulation from the conductor for a distance of 30 mm z Slightly round ...

Reviews: