Nexa ZRT-106 Quick Manual Download Page 2

4. 

The TRV can be mounted at various orientation as shown below: 

 
 
 
 
 
 
 
 
 
 
 
 
 

Note

: The TRV needs a free flow of air to sense the temperature so they must not be covered by 

curtains or blocked by furniture 

 
Calibration 
 

1. 

The unit supports SmartStart function, SmartStart enabled products can be added into a Z-Wave 
network by scanning the Z-Wave QR Code present on the product with a controller providing 
SmartStart inclusion. No further action is required and the SmartStart product will be added 
automatically within 10 minutes of being switched on in the network vicinity. 

 
2. 

After finished inclusion, the unit will start initializing itself. During this period the LCD will display

 

INIL 

with backlight flashing for 2 minutes. 

3. 

When the TRV displays 

AdAP

, press 

UP

 button to start the calibration. The number 

0

 will change to 

number 

1

. If it does not change to 

1

, press 

UP

 button again. 

4. 

The TRV will start to adapt itself to the stroke of the valve

’s body by opening and closing the valve 

twice to store the end points. This could take up to 1 minute. 

 
 
 
 
 

 

 

 

5. 

Calibration is complete when temperature readings appear on the LCD. 
 

Note

:   

1) Temperature readings will become accurate 10 minutes after installing the batteries. 

2) Make sure use new batteries to perform calibration to ensure the normal operation of the motor. 
 

Operation 
 

1. 

The user can choose between two heat levels for automatic temperature control without user 
intervention. This can be selected either by button 

or set through the gateway. 

 

“HEAT” mode

: This is a higher temperature level for indoor comfort and normally used when a 

room is occupied. 
 

“ENERGY HEAT” mode

: This is the lower temperature level for energy saving, typically used 

during sleeping or when a room is empty. 
 
Setpoints for these two modes must first be preset through the gateway. The TRV will activate 
heating whenever room temperature falls below these setpoints. 
 

2. 

User can use the gateway’s scheduler or scenes controller to switch between these two modes at 
anytime depending on their lifestyle. Refer to the gate

way’s instruction manual for this. 

 

3. 

Manual Over-ride

: the user can override the preset settings at anytime allowing for on-demand 

manual control of the TRV. Pressing the 

Up, Down

 and 

M

 button on the TRV will bypass the 

setpoints temporarily for 4 hours (Configure 10). After 4 hours, it will restore the last mode and 
temperature. 

 

4. 

Open window detection

: When enabled, the TRV will automatically stop heating when it detects a 

sudden drop in room temperature (default: 2°C in 15 minutes). This usually happens when a 
window or door is opened without turning off the heating device. The LCD will display 

OP

The device will return to the previous mode of operation after 30mins, or press any button to exit. 
 

5. 

Key lock

: When enabled, the button keys on the TRV will be locked to prevent any tampering, 

shown by the 

LOCK

 icon on the LCD. Key lock can also be activated by pressing and hold buttons 

P

 and 

M

 simultaneously for 5 seconds.

 

 

6. 

OFF

: This mode turns off the thermostat control of the TRV. Note that this does not switch off the 

device itself. 

 

Maintenance 

 

Low Battery

: Under low battery condition, the TRV will remit RF signals to the gateway to alert the user 

of its low battery condition. Replace the batteries as soon as possible. 
 

Decalc

 : When the TRV is inactive for long periods in use, e.g. during summer, it will automatically rotate 

the valve once every two weeks. This helps to prevent clogging of the radiator pipes and stiffening of the 
valve caused by build up of minerals. 

 
Programming 

Z-Wave Group 

The TRV supports1 Association Group: 

Group 1

: Association with 1 Controller node. 

Group 1 command: 

 

When the unit is powered up first time, the unit will send a Notification Report and Clock report to 
the node of Group 1. 

 

When the battery level of the unit drops to an unacceptable level, the unit will emit Battery report to 
the nodes of Group 1. 

 

When performing Factory Reset the unit will send Device Reset Locally Notification to the node of 
Group1. 

 

The unit will send Sensor Multilevel Report to the node of Group 1 every two hours. 

 

When changing mod of the unit, it will send Thermostat Mode Report to the node of Group 1. 

 

When changing target value of temperature, the unit will send Thermostat Setpoint Report to the 
node of Group 1. 

 

When changing the state of button lock, the unit will send Protection Report to the node of Group 
 
 

 

 

 