Newton Waterproofing Control Panel-Pro Operational Manual Download Page 8

14

For more information visit us online www.newtonwaterproofing.co.uk

Call us for more information on +44 (0)1732 360095

15

SERVICE DUE SETTING

The engineer can select the service due function by adding a jumper  to both service timer contacts. This will 

time down from 365 days to “service due” (will not time days when the panel is not powered up). To reset 

the service timer, add jumper links to both service timer and display reset links. Press and hold down the 

reset buttons until the display reads memory reset. You have to do this for each pump display. If service due 

setting is NOT required do not place the jumpers on the two “service timer” links. See below for position of 

service timer & display reset jumper links.

RESETTING COUNTER MEMORY AND SERVICE TIMES

To reset the counter and hour meters, link the display reset jumper and remove the service timer link. Press 

the rest button until the display reads memory reset. After resetting, replace the service timer link & remove 

the display reset link.

Pump 1 Jumper Settings

Display
Link

Service 
Timer
Link

Pump 2 Jumper Settings

Display
Link

Service 
Timer
Link

DISPLAY INFORMATION

1. PUMP CYCLES & PUMP HOURS RUN - (Default display) Displays the cycles and running hours for each 

pump from date of installation or engineer reset
2. HIGH CURRENT - Warning of a pump pulling more current than normal. This information may be displayed 

when both pumps are running or in mains failure mode. CALL ENGINEER only if this information is displayed 

in normal use for longer than 24 hours
3. WATER HIGH ALARM - This warning happens when:

A. The water level reaches the small alarm float or the wires to the alarm float have been cut

B. The main float has failed or the wires to the main float have been cut

C. Both pumps have failed and no water is being pumped from the sump chamber

DANGER OF FLOODING - CALL ENGINEER. Check power is on to the Panel, check cables and float switches, 

check any fuses. Requires both reset buttons to be pressed to reset the warning
4. MAINS FAILURE - Grid mains to the Panel is off and it is running on emergency power from the Power 

Converter and battery. The alarm will beep once per minute after a pump cycle during mains failure. 

Depending on the amount of water flow, battery age and condition, the running time from one battery can 

vary from minutes to days. Auto-reset on power restoration
5. PUMP FAULT - This indicates that one of the pumps is either not connected, damaged, pumping air, or 

an internal pump protection fuse has blown (10 A) due to a major pump fail. The alarm will BEEP twice per 

minute, 30 seconds after the pump failure. CALL ENGINEER. Press both reset buttons to reset
6. PUMP CURRENT, BATTERY VOLTS - This information is only displayed when a pump is running. The 

information is for the engineer to monitor the current that each pump is using and the condition of the 

backup battery voltage. This information is also useful in mains fail mode to check the back up battery 

voltage when a pump is running. The voltage in normal use on grid mains should be 13.5 -14.8 Volts, this 

indicates the back up battery is being charged
7. SOUNDER OFF - This information warns the user the alarm sounder has been MUTED. If the alarm sounder 

is active and cannot be reset, CALL ENGINEER
8. DISPLAY BACK-LIGHT - The back-light will be on low when the panel is powered up. The back-light will go 

bright to indicate which pump is running, the display will show the pump current and battery voltage
9. SERVICE DUE - This information indicates the service option has been activated by the engineer and the 

annual pump service is now due. CALL ENGINEER
Note, warning information or alarm sounders can be reset by pressing the reset buttons (it will not reset if 

pressed while the display back-light is bright or the pumps are running). The reset will only happen if the 

reason of the warning has been corrected. If it cannot be reset, CALL ENGINEER.

To MUTE the sounders: Each display has its own internal warning sounder and the panel has one main 

alarm sounder. ONLY MUTE THE SOUNDERS IF YOU ARE SURE. CALL ENGINEER IF THE PANEL INDICATES 

A FAULT OR SOUNDS AN ALARM YOU CANNOT RESET.
To mute an alarm: Press the mute buttons twice on each pump when the pumps are not running. This 

will mute the sounder for 12 hours only. To remind the user of a muted fault, the mute function will 

cancel after 12 hours. YOU CAN ONLY MUTE THE SOUNDER WHEN THE PUMP(S) ARE NOT RUNNING.

TO CANCEL MUTE (sounder off), turn both grid mains and inverter mains off for approximately 5 seconds. 

This will reset the mute function.
OPERATING A PUMP MANUALLY . To operate each pump manually, press the pump button. The display 

back-light will brighten and the display will show pump current in amps and the backup battery voltage. 

Both pumps can be operated if the panel is operating on mains power. If the panel is powered via the 

Power Converter and battery, the panel (with default settings) will allow one pump to operate at a time.

ENGINEER OPTIONS

USER INSTRUCTIONS

Summary of Contents for Control Panel-Pro

Page 1: ...Pumps Pumping Systems and Ancillaries NEWTON CONTROL PANEL PRO CP2 CP7 Multi Function Pump Control and Monitoring Panel Rev 3 3 19 July 2017 Newton Waterproofing Systems Operational Manual...

Page 2: ...from area to area or jurisdiction to jurisdiction The manufacturers responsibility for malfunctions and defects in the product is limited to repair and replacement as set forth in this warranty state...

Page 3: ...stable master timer setting to accommodate different sized sumps There is also the option to prevent both pumps running at the same time if the system is running from backup battery 5 Automatic curren...

Page 4: ...r that a service is due on the system this function can be selected by the engineer 16 All float switches are 12 VDC low voltage Via two separate isolation transformers 17 Each pump has a manual overr...

Page 5: ...Earth This installation MUST be earthed This control panel is not waterproof is of a metal construction and must be installed in a dry well ventilated area Warning It is important to read and underst...

Page 6: ...always closed and only opens when lifted upwards by rising water Both the Level and Alarm floats have two wires The connection of these wires is not dependent on polarity and can be fitted to either o...

Page 7: ...charge The Inverters are silent except when in Bulk Mode INSTALLATION OF POWER INVERTERS Power Inverters must be stored in dry conditions before installation Power Inverters must be installed in a dr...

Page 8: ...one of the pumps is either not connected damaged pumping air or an internal pump protection fuse has blown 10 A due to a major pump fail The alarm will BEEP twice per minute 30 seconds after the pump...

Page 9: ...and the battery connections H The condition of the Power Inverter if fitted test backup system by turning off the mains to both the Panel and Power Converter I Test the Dialer if installed J Reset ser...

Page 10: ...18 For more information visit us online www newtonwaterproofing co uk Call us for more information on 44 0 1732 360095 19 PANEL INTERNAL WIRING DIAGRAM...

Page 11: ...rt of our policy of continuous product improvement we reserve the right to change our specifications at any time Newton Waterproofing Systems Is A Trading Name Of John Newton Company Ltd Newton House...

Reviews: