B) Real Time Clock
RTC Date and Time:
The formats are
mm/dd/yyyy
and
hh:mm:ss
. The exact formats
are required otherwise an error message will appear in the Title box. Note: time is
military time/24 hour based.
Adjust RTC Only:
If checked, the clock will be updated and nothing else, provided
that “
Activation
” is set to “
Status/RTC/Alarm
”. To verify the clock, set the “
Activation
”
to “
Configuration
”, click
Update
button, then set “
Activation
” to “
Status/RTC/Alarm
”
and click
Update
button one more time.
Time Stamp:
If checked, the Humidity/Temperature/Dewpoint values will be stamped with
time and date using Port 1000 (HTTPget program must be used, see
Section 4.5.1
).
Secured Applet:
If checked, the LOGIN password is required to open “Read Sensor” and
“Chart” pages.
C) Flash Card Size:
Reports the Flash Card density and if it is already recorded, how many
locations are filled.
0-Megabytes:
Flash Card is not installed or a bad Flash Card
2-Megabytes, 4-Megabytes, 8-Megabytes:
available sizes of Flash Cards.
D) Flash Card Message:
Describes RTC setup, listed in the previous 4 scenarios.
Flash Card Module Malfunctional
Open Sensor
Flash Card Standby
Flash Card Recording Stopped
Flash Card Pre-Recorded
Flash Card Recording Complete
Flash Card Recording On
Wait Reading Flash
Flash Card Module Not Initialized
Recording Initialized
Flash Card Corrupt Initialization
If the battery is not connected or the voltage is low, the statement “
Low Battery
” will
be added to the above statements. You may also see a statement “
Archive Busy
” if
another client is busy receiving archive data. In this case, refrain from activating the
applet, instead keep clicking the
Update
button and make sure “
Activation
” is set to
“
Status/RTC/Alarm
” until the “
Archive Busy
” statement is no longer displayed.
E) Alarm Setup:
There are two alarms which can be assigned to temperature or humidity.
Alarm Type:
Selection of Temperature (T) or Humidity (H) and Above Setpoint (Hi) or
Below Setpoint (Lo):
T&T:Hi/Lo
T&H:Hi/Lo
T&H:Hi/Hi
H&H:Hi/Lo
T&H:Lo/Hi
T&H:Lo/Lo
No Alarm
Example:
If T&T:Hi/Lo is selected, the temperature will be monitored against these
two Hi and Lo values. If temperature goes above Hi value, Relay 1 will be energized,
and if temperature goes below Lo value Relay 2 will be energized.
Alarm Enabled:
Selections of
“Latched ”
or
“Unlatch”
are available. If “
Unlatch
” is
selected, the relay in the iServer will be turned on (closed) when the temperature and/or
humidity values fall outside of Setpoint range. When the temperature and/or humidity
values are back within the range, the relay will be turned off (opened).
If “
Latched
” is selected, the relay in the iServer will be turned on (closed) when the
temperature and/or humidity values fall outside of Setpoint range and will remain on until
the user turns it off.
SP1 and SP2:
Editable box for Setpoint values. The format is
nnn.n
, it must be followed
exactly otherwise the modification will not take place for any modified item in the Alarm Setup.
22