Page 25
FEATURES AUTOFILL CONFIGURATION SCREENS
The Password Access Screen is displayed to
provide access to advanced system
configuration screens. The advanced
configuration screens contain control settings
that should only be changed by qualified
individuals.
FEATURES AUTOFILL CONFIGURATION SCREEN 1
The first Autofill Configuration screen is
accessed by pressing the Autofill Configuration
Button located on the Features Configuration
Screen and entering the correct password or by
pressing the “Prev” Button located
on the second Autofill Configuration screen.
This screen allows you to change the following
settings:
Start Level
(Numeric Percentage Value)
This is the Fresh tank level setting to trigger
the refill function. If the Auto Fill function is
Enabled and the Fresh tank level drops below
this value, the fill valve will open to refill the
tank.
Select value using the Up / Down Arrows
Stop Level
(Numeric Percentage Value)
This is the Fresh tank level setting to trigger
the tank full function. If the Auto Fill function
is Active and the Fresh tank level rises above
this value for the Run After time setting, the
fill valve will close to stop filling the tank.
Select value using the Up / Down Arrows
Max Time Out (Numeric min Time Value)
If the Auto Fill Function is Enabled and the
Fresh Tank is not filling, this setting controls
the amount of time the Fill Valve will be held
on if the city pressure switch opens (no city
pressure) or if the Fresh Tank is not filling fast
enough. If the Fresh Tank does not fill fast
enough, the system will assume that there is
a plumbing leak and Disable the Auto Fill
function.
Select value using the Up / Down Arrows
Run After Minutes
(Numeric min Time
Value)
This setting determines the number of
minutes to hold the fill valve on after the Stop
Level has been reached. The Run After
function allows for pressure equalization in
the Fresh tank after the fill level is reached. If
this value is set to low, the tank level value
will read below the Stop Level setting. If this
value is set to high, the tank level value will
read higher that the Stop Level or the tank
will over flow.
Select value using the Up / Down Arrows
Summary of Contents for SilverLeaf RV-C Control System
Page 1: ...2012 Newmar Corporation October 2011 SilverLeaf RV C Control System Training Manual ...
Page 2: ......
Page 41: ...Page 39 ALL ELECTRIC OPTION LP STANDARD ...
Page 43: ...Page 41 ...
Page 44: ...Page 42 ...
Page 45: ...Page 43 EXDP TANK CAPACITIES KGDB TANK CAPACITIES ...
Page 46: ...Page 44 ...
Page 47: ...Page 45 ...
Page 48: ...Page 46 ...
Page 49: ...Page 47 ...
Page 50: ...Page 48 ...
Page 51: ...Page 49 ...
Page 52: ...Page 50 ...
Page 53: ...Page 51 ...
Page 54: ...Page 52 ...
Page 55: ...Page 53 ...
Page 56: ...Page 54 ...
Page 57: ...Page 55 ...
Page 58: ...Page 56 ...
Page 59: ...Page 57 ...
Page 60: ...Page 58 Blank Page ...