38

SV01C

Troubleshooting and Diagnostics

Fault

Cause

Remedy 

(1)

Digital Input  
Configuration fault (P11...
P13)

More than one digital input set for the 
same function

Each setting can only be used once (except 
settings 0 and 3)

Only one digital input configured for MOP 
function (Up, Down)

One input must be set to MOP Up,  another 
must be set to MOP Down

PID mode is entered with setpoint 
reference and feedback source set to the 
same analog signal 

Change PID setpoint reference (P11…
P13) or feedback source (P01).

One of the digital inputs (P11…P13) is 
set to 10 and another is set to 11…14.

Reconfigure digital inputs

One of the digital inputs (P11…P13) 
is set to 11 or 1 and another is set to 
13 or 14.
PID enabled in Vector Torque mode (P00 
= 1 or  and  P300 = 5)

PID cannot be used in Vector Torque mode

Remote keypad fault

Remote keypad disconnected

Check remote keypad connections

L

Low DC Bus Voltage fault

Mains voltage too low

Check mains voltage

1

No Motor ID fault

An attempt was made to start the drive 
in Vector or Enhanced V/Hz mode prior to 
performing the Motor Auto-calibration

See P300…P399 for Drive Mode setup 
and calibration.

Module communication fault

Communication failure between drive and 
Network Module.

Check module connections

 

Network Faults

Refer to the module documentation. for 
Causes and Remedies.

Output fault: 
Transistor fault

Output short circuit

Check motor/motor cable

Acceleration time too short

Increase P104, P15

Severe motor overload, due to:
•  Mechanical problem
•  Drive/motor too small for application

•  Check machine / system
•  Verify drive/motor are proper size for 

application

Boost values too high

Decrease P168, P169

Excessive capacitive charging  current of 
the motor cable

• 

Use shorter motor cables with lower 
charging current

•  Use low capacitance motor cables
•  Install reactor between motor and drive

.

Failed output transistor

Contact factory technical support

Output fault:  Ground fault

Grounded motor phase

Check motor and motor cable

Excessive capacitive charging  current of 
the motor cable

Use shorter motor cables with lower 
charging current

Motor Overload fault

Excessive motor load for too long

•  Verify proper setting of P108
• 

Verify drive and motor are proper size 
for application

(1)   The drive can only be restarted if the error message has been reset

Summary of Contents for Rhino RM250

Page 1: ...RhinoResurfacing Machine Operator s Manual RS150 1 5HP RM250 3HP...

Page 2: ...For your personal safety READ and UNDERSTAND before using SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE...

Page 3: ...nvites accidents Personal Safety 7 Stay alert watch what you are doing and use common sense when operating equipment Do not use equipment while tired or under the influence of drugs alcohol or medicat...

Page 4: ...use 12 gauge cord or larger If in doubt use the next heavier gauge The smaller the gauge number the heavier the cord SPECIFIC SAFETY RULES DO NOT let comfort or familiarity with product gained from re...

Page 5: ...right side of the handle control box to adjust speed of equipment Before starting the equipment ensure that the speed is set to the lowest speed available as displayed on the VFD screen Doing so will...

Page 6: ...ush This will ensure maximum adhesion Check that the handle bolts are tight Vacuum or wipe underside of machine Inspect plug ends for signs of carbon deposits or arcing Check all fasteners and tighten...

Page 7: ...g but not limited to engines motors electrical components transmissions etc shall carry the accesso ry manufacturers own warranty New Grind Inc will at its option repair or replace at the New Grind In...

Page 8: ...conditions pursu ant to which the purchaser Purchaser will purchase and New Grind Inc Seller will sell the products accessories attach ments collectively the products ordered by the Purchaser These t...

Page 9: ...ss or damage during shipment are to be filed with carrier by the Purchaser Seller will not assume responsibility for the performance of the carrier Backorders will be shipped in the most practical fas...

Page 10: ...agreements correspondence quotations or under standings heretofore in force between the parties relating to the subject matter hereof There are no agreements between Seller and Purchaser with respect...

Page 11: ...www newgrind com...

Page 12: ...SV01C Operating Instructions SMVector Frequency Inverter...

Page 13: ...le parameter version d Dynamic Braking fault Dynamic braking resistors are overheating Increase active decel time P105 P126 P127 Check mains voltage and P107 External fault P121 P123 21 and that digit...

Page 14: ...r to performing the Motor Auto calibration See P300 P399 for Drive Mode setup and calibration Module communication fault Communication failure between drive and Network Module Check module connections...

Page 15: ...mpt P110 5 or 6 Check motor load Single Phase fault A mains phase has been lost Check mains voltage Start fault Start command was present when power was applied P110 0 or 2 Must wait at least 2 second...

Page 16: ...AC Technology Corporation 630 Douglas Street Uxbridge MA 01569 USA 1 508 278 9100 SV01C...

Reviews: