
25
25
Use the following procedure for initial start-up of the boiler:
1) Make sure that the boiler is filled with water to the normal water line (28 3/4 inches above the floor or pad on which the
boiler is installed)
2) Check all new gas piping for leaks and purge piping sections that are filled with air. See Part 4 of the
National Fuel Gas
Code
for additional information on testing and purging gas lines.
3) Verify that vent system is complete and free of obstructions before attempting to fire boiler.
4) Inspect all wiring for loose or uninsulated connections.
5) Make sure the main burners are seated properly in the rear of burner tray and on orifices.
6) Adjust steam pressure limit control for a cut-in pressure of 0.5 psi and a differential pressure of 1 psi.
7) Adjust thermostat to the highest setting.
8) Start the boiler using the Operating Instructions. See Figure 19.
9) Upon initial start-up, the gas train will be filled with air. Even if the gas line has been completely purged of air, it
may take several tries for ignition before a flame is established. Once a flame has been established for the first time,
subsequent calls for burner operation should result in a flame on the first try.
10) Observe pilot burner flame. Pilot burner produces three flames. The center one should be a steady medium blue flame
covering around 3/8” to ½” of spark electrode/flame rod. See Figure 18.
12) Make sure vent damper is in open position when main burners are firing.
13) Inspect the main burner flames visible through the observation port in burner access panel. The flame should be stable
and mostly blue (see Figure 20). No yellow tipping should be present; however, intermittent flecks of yellow and orange
in the flame are normal.
14) Check entire gas train for leaks using soap and water or other approved leak detection method while boiler is firing. Fix
any leaks found immediately.
15) Run gas valve safety shutdown test. With main burners firing, disconnect ignition cable from ignition module. Both
pilot burner and main burners should stop firing.
WARNING
•
NEVER USE A FLAME TO CHECK FOR GAS LEAKS.
•
MAKE SURE THAT THE AREA AROUND THE BOILER IS CLEAR AND FREE FROM
COMBUSTIBLE MATERIALS, GASOLINE, AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
•
DAMPER MUST BE IN OPEN POSITION WHEN APPLIANCE MAIN BURNER IS OPERATING.
XI. System Start-up
Summary of Contents for CGS-C Series
Page 24: ...24 FIGURE 17 WIRING DIAGRAM McDONNELL MILLER MODEL 67 LOW WATER CUTOFF X Electrical continued...
Page 27: ...27 27 FIGURE 19 OPERATING INSTRUCTIONS XI System Start up continued...
Page 35: ...35 35 XIII Troubleshooting continued...
Page 37: ...37 37 XIII Troubleshooting continued...
Page 39: ...39 39...
Page 41: ...41 41 XIV Repair Parts continued...
Page 43: ...43 43 XIV Repair Parts continued...
Page 45: ...45 45 XIV Repair Parts continued...
Page 47: ...47 47 XIV Repair Parts continued...
Page 49: ...49 49 XIV Repair Parts continued...
Page 51: ...51 51...
Page 52: ...52...