Shanghai New Rock Technologies, Inc.
Page 12/23
Figure 2-2 Installation Flowchart in the Cabinet
2.2
Workbench Mounting
2.2.1
Install MX8 on the Workbench
MX8 can be placed on a clean and flat workbench, please ensure the stability and good ventilation
conditions of the workbench.
2.2.2
Install MX51, MX100-AG, and MX120 on the Workbench
MX51, MX100-AG, and MX120 are designed to be installed in the cabinet, but they also can be
installed on the workbench under the condition of meeting the installation conditions regulated in
Section 1.2. Please ensure the stability, fastness, and good ventilation and power supply conditions of
the workbench, and then flatly put the gateway equipment on the middle of the workbench.
2.3
Rack Mounting
The MX51, MX100-AG, and MX120 series chassis are designed to be mounted on a standard 19-inch
rack with 1U height.
2.3.1
Attaching the Brackets
Place the MX51, or MX100-AG, or MX120 series chassis on the workbench, take two L-shape rack
mounting brackets and screws, install the brackets at the left and right sides of the equipment, as
shown in the Figure 2-3.
The L-shape brackets are used to secure the gateway to the rack. The brackets cannot support the
weight of the equipment alone. Prior to install the MX51, or MX100-AG, or MX120 series chassis into
rack, a supporting shelf must be installed in place where the gateway will sit.
Start
Install the gateway to the cabinet
Connect the gateway to Ethernet
Connect POTS lines to FXO ports
Connect phone sets to FXS ports
Connect the grounding
Connect the gateway to power
End