Network Thermostat NetX X Series Installation And Programming Manual Download Page 4

WIRING DIAGRAM CROSS REFERENCE

CHART

The chart below list the connections needed for most

common applications. Refer to the Basic Wiring Diagram for

where to connect appropriate wires.

SPECIFICATIONS

RATED VOLTAGE:

20V to 30VAC, 24VAC nominal

RATED A.C. ⁄ D.C. CURRENT:

0.05 to 0.75 AC / 0.0 to 0.75 DC Amp continuous, per output,

surges to 3 Amps maximum

TEMPERATURE CONTROL RANGE: HEATING:

38 to 88°F (6 to 30°C) in 1° steps

COOLING:

60 to 108°F (16 to 40°C) in 1° steps

THERMOSTAT SENSING RANGE:

32˚F to 118°F (0˚C to 48°C) Control Accuracy: ±1°F @ 68°F (±0.5°C @ 20°C)

MINIMUM DEADBAND:

2°F (1°C)

DIMENSIONS:

5.1”H x 4.7”W x 1.15”D (130mm x 119mm x 29mm)

EQUIPMENT TERMINATIONS:

R - 24V switching voltage, W1 - Heat1 or Aux/Emergency Heat, G - Fan, Y1-Compressor1,

Y2 - Compressor2, O/W2 - Heat2 or Rev. Valve in Cooling, B - Rev. Valve in Heating

POWER TERMINATIONS:

24V - remote power (not used), 24V(c) - power common (from HVAC equipment)

HUMIDITY TERMINATIONS:

K - Independent Relay, H - Humidify, D - Dehumidify

INDEPENDENT RELAY TERMINATION:

K2 - Independent Relay

INPUT TERMINATIONS:

LED1 (Filter Icon Selectable), LED2 (Fault Icon Selectable)

OCCUPANCY TERMINATIONS:

CLK1 ( + ), CLK2 ( – )

REMOTE SENSOR TERMINATIONS:

RS+V - Power, RS2 - Return, RS1 - Data

COMMUNICATIONS TERMINATIONS:

X1 - XBus ( + ), X2 - XBus ( – )

WIRELESS RADIO:

2.4 GHz IEEE 802.11b/g, Security: WEP, WPA-PSK, and WPA2-PSK

FIVE (5) YEAR LIMITED WARRANTY

Network Thermostat™ warrants to the original purchaser that

this product will be free from defects in workmanship and

materials for a period of five years from the date of purchase

with proof of purchase.

Warranty Limitations

This warranty begins on the date of purchase.

Warranty is Void if:

The date code or serial number is defaced or removed.

The product has a defect or damage due to product

alteration, connection to an improper electrical supply,

shipping and handling, accident, fire, flood, lightning or other

conditions beyond the control of the manufacturer.

The product is not installed according to the manufacturers

instructions and specifications.

Owner’s Responsibility

Provide proof of purchase.

Provide normal care and maintenance.

Pay for freight, labor and travel.

Return any defective product.

In no event shall the manufacturer be liable for incidental or

consequential damages.

This warranty gives you specific legal rights and you may have

others which vary by state and/or province. For example, some

states and/or provinces do not allow the exclusion or limitation of

incidental or consequential damages, so this exclusion may not

apply to you. The manufacturer’s continuing commitment to quality

products may require a change in specifications without notice.

CA Title 24 Requirements

This thermostat meets the Joint Appendix 5 (JA5) requirements

for Occupant Controlled Smart Thermostat (OCST) certification

of the California Energy Commission (CEC).

FCC REGULATORY INFORMATION

This equipment complies with the limits for a Class B digital

device, pursuant to part 15 of the FCC rules. These limits are

designed to provide reasonable protection against harmful

interference in a residential installation. This equipment

generates, uses and can radiate radio frequency energy and, if

not installed and used in accordance with the instructions, may

cause harmful interference to radio communications. However,

there is no guarantee that interference will not occur in a

particular installation, If this equipment does cause harmful

interference to radio or television reception, which can be

determined by turning the equipment off and on, the user is

encouraged to try to correct the interference by one or more of

the following measures:

Reorient or relocate the receiving antenna.

Increase the separation between the equipment and receiver.

Connect the equipment into an outlet on a circuit different

from that to which the receiver is connected

Independent Power Source cont.

2. Place the separate transformer 24VAC wire in 24VAC

terminal.

3. Move the WiFi or Ethernet board RED wire from R to the

24VAC terminal.

4. Leave the WiFI or Ethernet board BLACK wire in the 24V(c)

terminal. If connected, remove thermostat wire from the

24VAC(c) terminal.

5. Place the equipment red wire in R.
6. Place the separate transformer 24VAC(Common) wire in

the 24V(c) terminal.

7. Common from equipment does not connect to thermostat.

This can cause a ground loop and issues.

WIFI

SETUP

STAT

L E D 1

L E D 2

C L K 1

C L K 2

R S 2

R S 1

R S + V

X 2

X 1

K 2

K / H / D

Y 2

W 1

Y 1

G

R

2 4 V

2 4 V ( c )

O / W 2

B

C

Line
Voltage

24 Vac

Transformer

R

HVAC

Equipment

2

+ -

Terminals

K/H/D

Y2

W1

Y1

G

R

24V(c) O/W2

B

K2

Conventional- Heat only Gas

X

X

X

Conventional- Heat only Electric

X

X

X

X

Conventional- Cool Only

X

X

X

X

Conventional- 1H/1C Gas

X

X

X

X

X

Conventional- 2H/2C Gas

X

X

X

X

X

X

X

Conventional- 1H/1C Electric

X

X

X

X

X

Conventional- 2H/2C Electric

X

X

X

X

X

X

X

Heat Pump- No Auxiliary Heat Cool Reversing Valve

X

X

X

X

X

Heat Pump- No Auxiliary Heat Heat Reversing Valve

X

X

X

X

X

Heat Pump- 1 Stage Standard Cool Reversing Valve

X

X

X

X

X

X

Heat Pump- 1 Stage Standard Heat Reversing Valve

X

X

X

X

X

X

Heat Pump- 1 Stage Dual Fuel Cool Reversing Valve

X

X

X

X

X

X

Heat Pump- 1 Stage Dual Fuel Heat Reversing Valve

X

X

X

X

X

X

Heat Pump- 2 Stage Standard Cool Reversing Valve

X

X

X

X

X

X

X

Heat Pump- 2 Stage Standard Heat Reversing Valve

X

X

X

X

X

X

X

Heat Pump- 2 Stage Dual Fuel Cool Reversing Valve

X

X

X

X

X

X

X

Heat Pump- 2 Stage Dual Fuel Heat Reversing Valve

X

X

X

X

X

X

X

Independent Relay, Humidify, Dehumidify

X

Independent Relay

X

X-Series

Reviews: