Network Thermostat NetX X Series Installation And Programming Manual Download Page 2

7. Reconnect power to the HVAC equipment. You are now

ready to configure your thermostat for operation.

C

WARNING

: Your thermostat is NOT ready to use. You

must complete the Thermostat Setup section before using

the thermostat. Failure to do this can result in damage to your

equipment.

THERMOSTAT SETUP

The

Dot Matrix Display

will provide feedback on the

User Menu

or

Installer Menu

configuration and selected

options. The

Up Button

J

and

Down Button

K

are used to

select parameters while the

LEFT ARROW

(Back Button) and

RIGHT ARROW

(Accept button) are used to accept settings

and navigate through the menu. At any time you

can

use the

CANCEL BUTTON

to leave the User or Installer Menu.

TOUCHSCREEN USER MENU SETTINGS

Tap the

Menu Button

D

on the lower left of the thermostat

touchscreen to access the

User Menu

. The Dot Matrix Area

will guide you through the User settings. To save a setting

and navigate to the next menu item, press the

Checkmark

Button

M

(Right Arrow). To return to the previous menu item,

press the

Back Button

L

(Left Arrow). Use the Up

J

and

Down

K

Buttons to select from the available options for each

setting.

Brightness - Screen Brightness

Select brightness of the touchscreen display.

Options:

Auto (default)

,

High

,

Medium

,

Low

Color - Display color

Select the color of your display. The default is Cyan.

Options:

Cyan

,

Purple

,

Yellow

,

White

,

Red

,

Green

, and

Blue

.

Display Complexity

There are three different resting display options.

Options:

Full:

(default)

Shows entire screen all the time

Minimal:

if nothing is noticed by the sensor for 5 seconds

only room temperature shows.

Dark:

if nothing is noticed by the sensor for 5 seconds the

whole screen goes blank.

1

2

3

Adjust Clock-12Hr or 24Hr Clock

Select between AM/PM or 24H time display. 12 Hr is the default.

°F or °C Temperature Display

Select between

°F

(Fahrenheit) or

°C

(Celsius) temperature

display.

°F

(Fahrenheit) is the default.

TOUCHSCREEN INSTALLER MENU SETTINGS

Press and hold the

Menu Button

D

on the lower left of the

thermostat touchscreen for 5 seconds to access.

Installer

Menu

will briefly display in the Dot Matrix Area followed by

Conventional/HP

.

To save a setting and advance to the next

menu item, press the Checkmark Button

M

(Right Arrow). To

return to the previous menu item, press the Back Button

L

(Left Arrow).

Conventional/ Heat Pump

Select between

Conventional

or

Heat Pump

operation.

Conventional is the default.

NOTE:

If Conventional is Selected Proceed to

Stages Cool

.

If

Heat Pump

is selected, proceed to

# of Compressors

.

Stages Cool

Select between

1

or

2 Stages Cool.

The value is displayed in

the main display. The default is 1.

Stages Heat

Select between

1 or 2 Stages Heat.

The value is displayed in

the

Main Display

. The default is 1.

Gas or Electric Heat

Select between

Gas

or

Electric

operation. Gas heat is the default.

NOTE:

If you selected Conventional Heat, proceed to

Minimum On Time

.

# of Compressors

Select between

1

or

2 Stage Compressor.

The value is

displayed in the main display. The default is 1.

Enable Aux/EHeat

Select between

Aux/EHeat Mode On

(default) or

Aux/EHeat

Mode Off

.

NOTE:

If the

Aux/EHeat ON

is selected, proceed to

Heat Pump

Option

. Otherwise, proceed to the

Minimum On Time

option.

Heat Pump Option

Select between

HP Regular

(default) or

HP Dual Fuel

.

If needed, the thermostat will perform the function of a fossil

fuel kit. When

HP Dual Fuel

is selected the thermostat will turn

off the compressor with a call for AUX heat. The

HP Regular

option will allow the compressor and AUX heat to run

simultaneously.

Minimum On Time

Select between

0-5 Minutes.

The value is displayed in the main

display. 0 Minutes is the default. The system will operate for a

minimum of 0 minutes to 5 minutes depending on your setting.

Minimum Off Time

Select between

2 to 5 Minutes.

The value is displayed in the

main display. 2 Minutes is the default. The system will allow

equipment recovery for 2 to 5 minutes before turning on again.

This is also known as short cycle protection.

Adaptive Recovery

Select

On

(default) or

Off.

When this is enabled, the thermostat

will anticipate when to turn on the heating or cooling system

prior to the start of a schedule in order to achieve the desired

setpoint temperature by the beginning of the schedule.

Fan Purge

Select between

Off, 30, 60, 90, 120 Seconds.

Off is the default.

1st Stage Differential

Select between

1-6˚F (0.5-3˚C).

The value is displayed in the

main display. 1˚F (0˚C) is the default. The 1st Stage Differential is

the temperature degree change required before the thermostat

responds.

2nd Stage Differential

Select between

1-6˚F (0.5-3˚C).

The value is displayed in the

main display. 1˚F (0˚C) is the default.

2nd Stage Delay

Select between

5-40 Minutes.

The value is displayed in the

main display. 20 Minutes is the default.

NOTE:

The following options only apply to multi-stage heat

pump configuration.

Aux Heat Diff

Select between

1-6˚F (0.5-3˚C).

The value is displayed in the

main display. 1˚F (0˚C) is the default.

Aux Heat Delay

Select between

5-40 Minutes.

The value is displayed in the

main display. 20 Minutes is the default.

High & Low Balance Point Configuration

If the thermostat is being used as a Heat Pump thermostat and

current weather conditions are enabled or an outdoor sensor is

connected to the remote sensor terminals, the thermostat can

be configured to disable the use of auxiliary heat during warmer

weather and to lock out the compressor during colder weather.

If the weather conditions are enabled the high and low balance

point settings are available in the installer menu.

B

TIP:

Refer to the manufacturer’s heat pump equipment

manual for temperature cut-offs on the equipment.

Low Balance Point

Select between

-54˚F to 39˚F (-48˚C to 4˚C).

The value is displayed

in the main display. This will lock out the heat pump at the

selected outdoor temperature. The default value is -54˚F (-48˚C).

High Balance Point

Select between

41˚F-118˚F (5˚C-48˚C)

. The value is displayed

in the main display. This will lock out the auxiliary heat at the

selected outdoor temperature. The default value is 118˚F (48˚C).

TOUCHSCREEN TEMPERATURE OVERRIDE

Temperature Override Range (During Lockout)

On the

Basic Configuration

page, this setting adjusts the

temperature variance allowed from the scheduled setpoint

when the faceplate locked. The range is from ±2˚F (1˚C) to ±8˚F

(4˚C). The default is ±3˚F (1.5˚C).

Temporary Override (Up to 24 hours)

Change the temperature setting temporarily without affecting

the schedules, both occupied and unoccupied. Use the Up

J

and Down

K

Buttons to adjust the temperature within the

minimum and maximum range. This temperature will be

maintained for the duration set by the

Override Timer.

To

cancel, simply press the Cancel Button.

I

Temporary Override During Lockout (Up to 24 hours)

Change the temperature setting temporarily without affecting

the schedules, even though the keypad is locked. Use the Up

J

and Down

K

Buttons to adjust the temperature limited to

the

Temperature Override Range

setting. This temperature

will be maintained for the duration set by the

Override Timer.

To cancel, simply press the Cancel Button.

I

A

NOTE:

If running an OCCUPIED schedule, the current

occupied setpoint will be shown, and if running an

UNOCCUPIED schedule the thermostat will revert to the most

previous OCCUPIED schedule setpoints.

ADDITIONAL SETTINGS AND FEATURES

In addition to the User Menu and Installer Menu The X-Series

thermostat has additional options that can be set using the

built-in web pages or via our cloud interface. Please refer to

this online guide for setting these additional parameters.

Unless otherwise noted, these additional settings are available

under the

Configuration

menu tab of the built-in web pages.

Override Timer

On the

Basic Configuration

page, you will be able to adjust

the length of a temporary override condition from 0 minutes to

24 hours, in 10 minute increments. The default override time is 8

hours.

Temperature Calibration Offset

The thermostat is pre-calibrated at the factory, but in some

installations, lack of airflow at the sensor or proximity to other

warming or cooling sources may cause the temperature to be

off by a few degrees. The X-Series thermostat includes a

temperature calibration offset with a range of ±6˚F (3˚C) in 0.2˚F

(0.1˚C) increments. The Temperature Calibration Offset is on

the

HVAC Settings

web page of the thermostat.

Page 2