7. Reconnect power to the HVAC equipment. You are now
ready to configure your thermostat for operation.
C
WARNING
: Your thermostat is NOT ready to use. You
must complete the Thermostat Setup section before using
the thermostat. Failure to do this can result in damage to your
equipment.
THERMOSTAT SETUP
The
Dot Matrix Display
will provide feedback on the
User Menu
or
Installer Menu
configuration and selected
options. The
Up Button
J
and
Down Button
K
are used to
select parameters while the
LEFT ARROW
(Back Button) and
RIGHT ARROW
(Accept button) are used to accept settings
and navigate through the menu. At any time you
can
use the
CANCEL BUTTON
to leave the User or Installer Menu.
TOUCHSCREEN USER MENU SETTINGS
Tap the
Menu Button
D
on the lower left of the thermostat
touchscreen to access the
User Menu
. The Dot Matrix Area
will guide you through the User settings. To save a setting
and navigate to the next menu item, press the
Checkmark
Button
M
(Right Arrow). To return to the previous menu item,
press the
Back Button
L
(Left Arrow). Use the Up
J
and
Down
K
Buttons to select from the available options for each
setting.
Brightness - Screen Brightness
Select brightness of the touchscreen display.
Options:
Auto (default)
,
High
,
Medium
,
Low
Color - Display color
Select the color of your display. The default is Cyan.
Options:
Cyan
,
Purple
,
Yellow
,
White
,
Red
,
Green
, and
Blue
.
Display Complexity
There are three different resting display options.
Options:
●
Full:
(default)
Shows entire screen all the time
●
Minimal:
if nothing is noticed by the sensor for 5 seconds
only room temperature shows.
●
Dark:
if nothing is noticed by the sensor for 5 seconds the
whole screen goes blank.
1
2
3
Adjust Clock-12Hr or 24Hr Clock
Select between AM/PM or 24H time display. 12 Hr is the default.
°F or °C Temperature Display
Select between
°F
(Fahrenheit) or
°C
(Celsius) temperature
display.
°F
(Fahrenheit) is the default.
TOUCHSCREEN INSTALLER MENU SETTINGS
Press and hold the
Menu Button
D
on the lower left of the
thermostat touchscreen for 5 seconds to access.
Installer
Menu
will briefly display in the Dot Matrix Area followed by
Conventional/HP
.
To save a setting and advance to the next
menu item, press the Checkmark Button
M
(Right Arrow). To
return to the previous menu item, press the Back Button
L
(Left Arrow).
Conventional/ Heat Pump
Select between
Conventional
or
Heat Pump
operation.
Conventional is the default.
�
NOTE:
If Conventional is Selected Proceed to
Stages Cool
.
If
Heat Pump
is selected, proceed to
# of Compressors
.
Stages Cool
Select between
1
or
2 Stages Cool.
The value is displayed in
the main display. The default is 1.
Stages Heat
Select between
1 or 2 Stages Heat.
The value is displayed in
the
Main Display
. The default is 1.
Gas or Electric Heat
Select between
Gas
or
Electric
operation. Gas heat is the default.
�
NOTE:
If you selected Conventional Heat, proceed to
Minimum On Time
.
# of Compressors
Select between
1
or
2 Stage Compressor.
The value is
displayed in the main display. The default is 1.
Enable Aux/EHeat
Select between
Aux/EHeat Mode On
(default) or
Aux/EHeat
Mode Off
.
�
NOTE:
If the
Aux/EHeat ON
is selected, proceed to
Heat Pump
Option
. Otherwise, proceed to the
Minimum On Time
option.
Heat Pump Option
Select between
HP Regular
(default) or
HP Dual Fuel
.
If needed, the thermostat will perform the function of a fossil
fuel kit. When
HP Dual Fuel
is selected the thermostat will turn
off the compressor with a call for AUX heat. The
HP Regular
option will allow the compressor and AUX heat to run
simultaneously.
Minimum On Time
Select between
0-5 Minutes.
The value is displayed in the main
display. 0 Minutes is the default. The system will operate for a
minimum of 0 minutes to 5 minutes depending on your setting.
Minimum Off Time
Select between
2 to 5 Minutes.
The value is displayed in the
main display. 2 Minutes is the default. The system will allow
equipment recovery for 2 to 5 minutes before turning on again.
This is also known as short cycle protection.
Adaptive Recovery
Select
On
(default) or
Off.
When this is enabled, the thermostat
will anticipate when to turn on the heating or cooling system
prior to the start of a schedule in order to achieve the desired
setpoint temperature by the beginning of the schedule.
Fan Purge
Select between
Off, 30, 60, 90, 120 Seconds.
Off is the default.
1st Stage Differential
Select between
1-6˚F (0.5-3˚C).
The value is displayed in the
main display. 1˚F (0˚C) is the default. The 1st Stage Differential is
the temperature degree change required before the thermostat
responds.
2nd Stage Differential
Select between
1-6˚F (0.5-3˚C).
The value is displayed in the
main display. 1˚F (0˚C) is the default.
2nd Stage Delay
Select between
5-40 Minutes.
The value is displayed in the
main display. 20 Minutes is the default.
�
NOTE:
The following options only apply to multi-stage heat
pump configuration.
Aux Heat Diff
Select between
1-6˚F (0.5-3˚C).
The value is displayed in the
main display. 1˚F (0˚C) is the default.
Aux Heat Delay
Select between
5-40 Minutes.
The value is displayed in the
main display. 20 Minutes is the default.
High & Low Balance Point Configuration
If the thermostat is being used as a Heat Pump thermostat and
current weather conditions are enabled or an outdoor sensor is
connected to the remote sensor terminals, the thermostat can
be configured to disable the use of auxiliary heat during warmer
weather and to lock out the compressor during colder weather.
If the weather conditions are enabled the high and low balance
point settings are available in the installer menu.
B
TIP:
Refer to the manufacturer’s heat pump equipment
manual for temperature cut-offs on the equipment.
Low Balance Point
Select between
-54˚F to 39˚F (-48˚C to 4˚C).
The value is displayed
in the main display. This will lock out the heat pump at the
selected outdoor temperature. The default value is -54˚F (-48˚C).
High Balance Point
Select between
41˚F-118˚F (5˚C-48˚C)
. The value is displayed
in the main display. This will lock out the auxiliary heat at the
selected outdoor temperature. The default value is 118˚F (48˚C).
TOUCHSCREEN TEMPERATURE OVERRIDE
Temperature Override Range (During Lockout)
On the
Basic Configuration
page, this setting adjusts the
temperature variance allowed from the scheduled setpoint
when the faceplate locked. The range is from ±2˚F (1˚C) to ±8˚F
(4˚C). The default is ±3˚F (1.5˚C).
Temporary Override (Up to 24 hours)
Change the temperature setting temporarily without affecting
the schedules, both occupied and unoccupied. Use the Up
J
and Down
K
Buttons to adjust the temperature within the
minimum and maximum range. This temperature will be
maintained for the duration set by the
Override Timer.
To
cancel, simply press the Cancel Button.
I
Temporary Override During Lockout (Up to 24 hours)
Change the temperature setting temporarily without affecting
the schedules, even though the keypad is locked. Use the Up
J
and Down
K
Buttons to adjust the temperature limited to
the
Temperature Override Range
setting. This temperature
will be maintained for the duration set by the
Override Timer.
To cancel, simply press the Cancel Button.
I
A
NOTE:
If running an OCCUPIED schedule, the current
occupied setpoint will be shown, and if running an
UNOCCUPIED schedule the thermostat will revert to the most
previous OCCUPIED schedule setpoints.
ADDITIONAL SETTINGS AND FEATURES
In addition to the User Menu and Installer Menu The X-Series
thermostat has additional options that can be set using the
built-in web pages or via our cloud interface. Please refer to
this online guide for setting these additional parameters.
Unless otherwise noted, these additional settings are available
under the
Configuration
menu tab of the built-in web pages.
Override Timer
On the
Basic Configuration
page, you will be able to adjust
the length of a temporary override condition from 0 minutes to
24 hours, in 10 minute increments. The default override time is 8
hours.
Temperature Calibration Offset
The thermostat is pre-calibrated at the factory, but in some
installations, lack of airflow at the sensor or proximity to other
warming or cooling sources may cause the temperature to be
off by a few degrees. The X-Series thermostat includes a
temperature calibration offset with a range of ±6˚F (3˚C) in 0.2˚F
(0.1˚C) increments. The Temperature Calibration Offset is on
the
HVAC Settings
web page of the thermostat.
Page 2