INDOOR
NT-URS
#1
OTHER
SENSORS
INDOOR
NT-URS
#2
INDOOR
NT-URS
#3
INDOOR
NT-URS
#4
INDOOR
NT-URS
#5
RS+V
RS2
RS1
AVG
RS+V
RS2
RS1
AVG
RS+V
RS2
RS1
AVG
RS+V
RS2
RS1
AVG
RS+V
RS2
RS1
AVG
RS+V
RS2
RS1
AVG
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
Secondary Internal Temperature Sensors
NT-DRS or NT-URS
Set as AUX3
NT-DRS or NT-URS
Set as AUX2
NT-URS
Set as AUX1
NT-URS
Set as HUMIDITY
Only
NT-URS
Set as INDOOR
Sensor
NT-URS
Set as OUTDOOR
Sensor
RS2 RS+V
RS1
To Thermostat
NT-URS Wiring Instructions
●
Only 1 Sensor for each type per thermostat except for INDOOR Sensor
●
All non indoor sensors and 1
st
INDOOR
sensor wired to RS1-to-RS1, RS2-to-RS2 and RS+V-to-RS+V
●
Additional
INDOOR
temperature sensors must be wired AVG-to-RS1, RS2-to-RS2 and RS+V-to-RS+V
●
Sensors can be placed in any order in the daisy-chain, except for multiple INDOOR sensors
WIRING DIAGRAM
COMPATIBILITY CHART
DIP SWITCH SETTINGS
SENSOR TYPE CONFIGURATION
INDOOR
Uses Internal
temperature sensor or
Indoor probe like the NT-
FS or NT-FS-S
OUTDOOR
Uses outdoor probe. Has
specific curve.Probe
connects to 2-screwless
terminals Ignores Temp/
Hum Sensor
INDOOR HUMIDITY
ONLY
Uses Internal Humidity
sensor.
AUX 1
Uses internal temperature
sensor or external probe.
The external probe
connects to 2-screwless
terminals
AUX 3
Uses internal temperature
sensor or external probe.
The external probe
connects to 2-screwless
terminals
AUX 2
Uses internal temperature
sensor or external probe.
The external probe
connects to 2-screwless
terminals
Multiple Configurations for Flexible Application Use
X7
X5
UP32
US32
INDOOR TEMPERATURE & HUMIDITY
Temp with internal sensor or external sensor (NT-FS, NT-RS-S)
• • •
INDOOR TEMP AVERAGE– up to 6 with automatic averaging
Temp with internal sensor or external sensor (NT-FS, NT-RS-S)
• • • •
HUMIDITY ONLY – (Internal Sensor)
5 to 95% Non-Condensing
• • •
OUTDOOR – Temperature Only (NT-OUTDOOR sensor required)
• • • •
AUX 1, AUX 2, AUX 3 – Temperature Only
(NT-PROBE-SS8 sensor. Inquire about other sensor types.)
• • •