Network Thermostat NetX NT-URS Installation Manual Download Page 3

MULTIPLE INDOOR SENSOR

CONFIGURATION

You can connect up to six (6) NT-URS sensors to provide

INDOOR temperature averaging in a large area or several

zones being controlled by the same system. Maximum

distance for all sensors is 300 ft. (90m). Follow the instructions

and diagrams to connect the additional INDOOR sensors.

A

NOTE:

: Only ONE (1) NT-URS sensor configured as an

INDOOR sensor can be added in this manner. Additional

INDOOR sensors may be added by using the AVG terminals.
1. Wire the first sensor using the single sensor instructions.

C

CAUTION:

Make sure there is no power to the sensors

by removing the thermostat from its backplate.

2. Connect wires to each additional sensor in the following

manner.

X-SERIES

UP32/US32

3. Set #SENSORS jumper to 1-2 for

ALL

additional sensors

used for averaging.

4. Reinstall the thermostat faceplate on to its backplate. Check

proper operation by watching the LED blink pattern as

outlined in the

LED Status

section. Repeat for each sensor.

ONE (1) YEAR LIMITED WARRANTY

Network Thermostat™ warrants to the original purchaser that

this product will be free from defects in workmanship and

materials for a period of five years from the date of purchase

with proof of purchase.

Warranty Limitations

This warranty begins on the date of purchase.

Warranty is Void if:

The date code or serial number is defaced or removed.

The product has a defect or damage due to product

alteration, connection to an improper electrical supply,

shipping and handling, accident, fire, flood, lightning or other

conditions beyond the control of the manufacturer.

The product is not installed according to the manufacturers

instructions and specifications.

Owner’s Responsibility

Provide proof of purchase.

Provide normal care and maintenance.

Pay for freight, labor and travel.

Return any defective product.

In no event shall the manufacturer be liable for incidental or

consequential damages.

This warranty gives you specific legal rights and you may have

others which vary by state and/or province. For example, some

states and/or provinces do not allow the exclusion or limitation of

incidental or consequential damages, so this exclusion may not

apply to you. The manufacturer’s continuing commitment to quality

products may require a change in specifications without notice.

SPECIFICATIONS

Rated Voltage:

20V to 30VAC, 24VAC nominal

Internal Temp Sensor Range:

+28°F to 119°F in 1° steps (-2°C to 48°C in 1° steps)

External Temp Sensor Range:

Outdoor: -54°F to +119°F (-48°C to +48°C);

Auxiliary Temp Sensor Range:

AUX1, AUX2, AUX3: -40°F to +200°F (-40°C to +93°C)

Internal Humidity Sensor Range:

5% to 95% Relative Humidity, Non-condensing

Measurement Accuracy:

Temperature: ± 1.0°F (±0.5°C);

Humidity: 0-90%RH (±3%) ; 20-80% RH (±2%)

Terminations:

RS1 - Data, RS+V – Power, RS2 – Return, 1 & 2 – External Temp

Sensor Leads, 1-2, 3-5, 6+ Sensors

Dimensions:

2.1”H x 2.85”W x 1.0”D (53mm x 73mm x 25.4mm)

Approved Cable Types:

CAT5 or CAT5e unshielded, or 1-Pair Twisted Shielded Cable

with Drain and nominal capacitance of 12pF/ft or less. Use riser

or plenum jacket as required by local code.
Maximum 300ft Total Sensor Cable Length per Thermostat

LED STATUS

The NT-URS includes a Diagnostic LED that can help you

troubleshoot your installation and sensor operation.

LED Off:

LED OFF indicates no power to the NT-URS or thermostat.

Check wiring of your sensor and the thermostat for problems.

Fix as necessary.

LED On Solid During Power-Up:

On power-up the LED will turn on solid until the NT-URS

successfully communicates with the thermostat. If the

connection is successful, the LED will blink according to its

configuration. If the remains on, there is a communication

problem. Check wiring and fix as necessary.

LED On Solid After Power Up:

If the NT-URS loses connection with the thermostat for 60

seconds, the LED will turn on solid. Check the wiring and fix as

necessary. Cycle power cycle power and recheck the LED

status.

LED Slow Blink (Onboard Sensor Operation):

If the NT-URS is configured to use its internal sensor

(temperature or humidity) the LED will blink each time the

thermostat requests data. This occurs approximately every 16-

20 seconds.

LED Double Blink (Onboard Sensor Averaging):

If the NT-URS is configured to INDOOR temperature and an

additional sensor is connected to the AVG connection, the LED

will blink twice each time the thermostat requests data. This

occurs approximately every 16-20 seconds.

LED Triple Blink (External Probe Operation)

If the NT-URS is configured to use an external probe

connected to the 2-screwless terminals, the LED will blink three

times the thermostat requests data. This occurs approximately

every 16-20 seconds.

LED Fast Continuous Blink (Lost External Probe)

If the NT-URS is configured to use an external probe and the

NT-URS loses communication with the probe, the LED will

continually blink fast. Check wiring and external probe and fix

as necessary.

A

NOTE:

In this condition, the NT-URS will stop reporting until

the communication with the external probe is fixed.

Page 3

OFF

ON

# Sensors

1-2

3-5

6+

UP

UP

OFF

ON

# Sensors

1-2

3-5

6+

UP

UP

NT-URS

Additional NT-URS Sensors

Set as Indoor Sensor for

Temperature Averaging

NT-URS

First NT-URS in chain

Set as Indoor Sensor

OFF

ON

# Sensors

1-2

3-5

6+

UP

UP

NT-URS

First NT-URS in chain

Set as Indoor Sensor

Wiring To

Next Sensor

Up to 4

additional NT-

URS Sensors

can be added

to this chain.

X-SERIES

UP32/US32

A

NOTE:

See

Page 2 Step 10 for

proper settings

A

NOTE:

Always

set additional

sensors to 1-2