Action: select from 

None

Heartbeat not used 

Power On – Latch 

Upon triggering, iBoot will power on and remain so until changed via 
the web, ibootctl.exe or direct messaging.

Power On – Follow 

Upon triggering, iBoot will power on.  When the heartbeat returns,
iBoot will power off. 

Power Off – Latch 

Upon triggering, iBoot will power off and remain so until changed via 

the web, ibootctl.exe or direct messaging. 

Power Off – Follow 

Upon triggering, iBoot will power off.  When the heartbeat response 
returns, iBoot will power on. 

Power Cycle 

Upon triggering, iBoot will cycle the power.  iBoot will wait the 
Heartbeat Frequency x Fail Count; if the heartbeat does not return, 
the power will be recycled again.  This will continue until the 
heartbeat returns or Heartbeat is turned off.  Make sure your 
Heartbeat frequency is longer than the time required to reboot your 
device.

Power Cycle Once 

Upon triggering, iBoot will cycle power one time. It will not cycle 
again automatically until the heartbeat returns and is lost again. 

Using Heartbeat Monitor 

With Heartbeat operational, the main iBoot page will display the current status of this feature.  The 
status will be OK to indicate that iBoot is receiving heartbeats, or that the fail counter has not yet 
been exceeded. 

If the fail count has been exceeded, the status will change to Triggered.  The Trigger Counter 
indicates the number of times the Heartbeat feature has been triggered.  A counter reset button is 
provided when logging in with the System password. 

Using the Heartbeat Program 

The heartbeat program and instructions are available from the distribution disk.

External Control Program 

NTI provides a remote control program to control iBoot directly.  This program is useful for 
creating simple desktop icons for specific power functions for one or more iBoots.  It can also be run 
from a command line and can be called by other programs. (Batch files etc.) 

For example, ibootctl.exe can be called from server monitoring programs such as WhatsUp Gold™, 
Servers Alive™ or any program that provides for an external program to be run upon loss of a 
server.

ibootctl.exe is available on the distribution disk.

Summary of Contents for ENVIROMUX PWR-RMT-RBT

Page 1: ...PWR RMT RBT Remote Power Reboot Switch Installation and Operation Manual ENVIROMUX Series NETWORK TECHNOLOGIES INCORPORATED Tel 330 562 7070 Fax 330 562 1999 1275 Danner Dr Aurora OH 44202 www networ...

Page 2: ...75 Danner Drive Aurora Ohio 44202 CHANGES The material in this guide is for information only and is subject to change without notice Network Technologies Inc reserves the right to make changes in the...

Page 3: ...Man095 Rev 10 23 07...

Page 4: ...Man095 Rev 10 23 07...

Page 5: ...pter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to rest on the power cord Do not locate this product where...

Page 6: ...bilities iBoot features several other means to operate automatically or under computer control Auto Ping The Auto Ping feature allows the switch to automatically detect failed Dual equipment and perfo...

Page 7: ...lectrical standards If the device to be powered uses an IEC320 receptacle and detachable power cord an IEC to IEC extension cord can be used The iBoot can be connected to a power strip to allow simult...

Page 8: ...work with iBoots on the same local subnets as the iBoots Once the iBoot Setup Utility is run click on Discovery to display all the iBoots on your network New iBoots will display with the name Set Loca...

Page 9: ...Boot Once an IP address is assigned you must check the DHCP server or use the iBoot Setup Utility to see what address is assigned to iBoot If you set the IP address using another method the address be...

Page 10: ...eturns host not responding 4 times then the address has not been programmed properly The process must be run within two minutes of powering up the iBoot and not have been set by a DHCP server Check th...

Page 11: ...abort a power cycle click on either Power On or Power Off buttons iBoot will assume the status selected If the Auto Ping or Heartbeat Features are in use then the page will also display the current s...

Page 12: ...If the new port is 9105 then use address http 192 168 1 254 9105 CallerIP 1 and 2 CallerIP provides IP address filtering to insure only authorized personnel access the iBoot You can set two IP address...

Page 13: ...ibootctl exe or direct messaging Power On Follow Upon triggering iBoot will power on When the ping response returns iBoot will power off Power Off Latch Upon triggering iBoot will power off and remain...

Page 14: ...t not to the Setup functions When this password is used the main screen will not have a link to Setup The System Password allows access to both the Main Screen and the Setup Screen The default for bot...

Page 15: ...t Confirmation The heartbeat can be generated in any of several ways A Windows executable program that will run as a tray applet that will transmit heartbeats at a steady interval to an iBoot A Window...

Page 16: ...the heartbeat returns and is lost again Using Heartbeat Monitor With Heartbeat operational the main iBoot page will display the current status of this feature The status will be OK to indicate that i...

Page 17: ...ir responses Command Format All of iBoot s commands follow the following format esc password esc action cr esc ASCII Escape character 1b hex or 27 decimal password The 1 to 10 character Power Control...

Page 18: ...0 A Max at 210 240 VAC Compliance UL cUL UL60950 Listed I T E File No E225914 CE Directives 89 336 EEC 92 31 EEC and 93 68 EEC EN 60950 3rd Edition EN 55022 1998 Class B FCC Part 15 Class B Network Du...

Reviews: