6
Example of Report configuration
FPort
:
0x07
Bytes
1
1
Var(Fix =9 Bytes)
CmdID DeviceType
NetvoxPayLoadData
CmdID
– 1 bytes
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
Description Device
Cmd
ID
Device
Type
NetvoxPayLoadData
ConfigRepo
rtReq
R718
WA
0x01
0x32
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte
Unit:0.1v)
Reserved
(4Bytes,Fixed
0x00)
ConfigRepo
rtRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte
Unit:0.1v)
Reserved
(4Bytes,Fixed
0x00)
(1)
Configure R718WA report parameters:
MinTime = 1min
、
MaxTime = 1min
、
BatteryChange = 0.1v
Downlink
:
0132003C003C0100000000 3C(Hex) =60(Dec)
Response
:
8132000000000000000000 (Configuration success)
8132010000000000000000 (Configuration failure)
(2)
Read Configuration:
Downlink
:
0232000000000000000000
Response
:
8232003C003C0100000000
(Current configuration)