7
5.2 Example of Config Report Time
FPort
:
0x07
Bytes
1
1
Var (Fix =9 Bytes)
CmdID
DeviceType
NetvoxPayLoadData
CmdID
– 1 byte
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
Description
Device
Cmd
ID
Device
Type
NetvoxPayLoadData
Config
ReportReq
R718MBC
0x01
0x2C
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
Reserved
(4Bytes,Fixed 0x00)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
Reserved
(4Bytes,Fixed 0x00)
(1)
Configure device parameters MinTime = 5 min, MaxTime = 5min, Battery Change = 0.1v
Downlink: 012C012C012C0100000000 // 012C (Hex) = 300(Dec)
The device returns:
812C000000000000000000 // Configuration is successful
812C010000000000000000 // Configuration failed
(2)
Read device parameters
Downlink: 022C000000000000000000
The device returns: 822C012C012C0100000000 // Current device parameters
5.3 Example of Config R718MBType
FPort
:
0x07
Description
Device
Cmd
ID
Device
Type
NetvoxPayLoadData
SetR718MB
TypeReq
R718MBC
0x03
0x2C
R718MBType(1Byte)
0x01_R718MBA
0x02_R718MBB
Reserved
(8Bytes,Fixed 0x00)