7
(1)
Configure the device parameter MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v, CurrentChange= 5mA
Downlink: 0122003C003C0105000000
Device Return:
8122000000000000000000 (configuration success)
8122010000000000000000 (configuration failure)
(2) Read the device parameter
Downlink: 0222000000000000000000
Device Return:
8222003C003C0105000000 (device current parameter)
5.3 Example for MinTime/MaxTime logic
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime MaxTime
S
leeping(MinTime)
S
leeping(MinTime)
Wakes up and collects data Wakes up and collects data Wakes up and collects data
REPORTS 3.6V REPORTS 3.5V REPORTS 3.6V
Note:
MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange value.
Example#2
based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
CurrentChange
(1byte Unit:1mA)
Reserved
(3Bytes,Fixed
0x00)