[ENG] UniPing server solution v4/SMS & UniPing server solution v3, User guide -[USS] Sensors Plugin
[USS] Sensors Plugin
–
[USS] Sensors Plugin
Sensors of 1-Wire Model Line
Sensors of a 1-Wire model line (
Humidity sensor 1-wire (HS), 2m
) are plugged
into 1W sockets by RJ12 plugs. It is allowed to use extenders and splitters. A maximum loop length of the 1-Wire
network is limited to 50 meters. It is possible to plug up to eight temperature sensors and up to four humidity
sensors to a device simultaneously.
Latest firmware work only with sensors with a 1-Wire interface (THS temperature sensor, HS humidity sensor, etc.).
Outdated firmware versions also supported temperature sensors of
series
as well, using the i2c interface.
An IR transceiver is connected by a four-line wire according to the table below:
Sensor
Flex
Sensor Flex
UniPing server solution v4/SMS
, UniPing
server solution v3
Terminal Block
Yellow
Labeled wire (red).
SCL
Green
Second wire after a labeled
one
SDA
Red
Third wire after a labeled
one
+5V
Black
Fourth wire after a labeled
one
GND
A sensor is shipped with an inseparable cable with connectors at the ends. A cable length can be extended using
, which are consequentially plugged one into another using any wire with a section no
less than 0,4 mm
2
. A maximum loop length is 10 meters from each sensor to a device (a «star» topology).
Dry contact sensors are door opening sensors, buttons and other sensors with a mechanism of work based on
opening/closing a conductor. A sensor is connected with two wires to an IO line of a device according to the table.
An order of plugging wires does not matter.
It is prohibited to plug sensors and external modules into NetPing devices when a power supply is on!
Configuring a device and receiving notifications from sensors are described in the document