[ENG] NetPing Input+Relay R404, User guide -[ENG] 7. [DKST 57]Connection of external sensors and actuators.
[ENG] 7. [DKST 57]Connection of external sensors and actuators.
–
The sensor comes with a non-detachable cable with lugs at the ends.
The cable length can be increased by
using
, which are connected in series into each other, or independently using any wire with a
cable section of at least 0.4 mm2. The maximum permissible loop length is 100 meters.
Airflow GRID 120 * 120 * 10mm NC
The sensor is a dry contact, so the order of wiring is irrelevant. The number of connected sensors is limited only by
the number of free IN lines.
Wire
Terminal
First wire
IN1 ... IN16
Second wire
GND
Depending on which input (IN1-IN16) the sensor is connected to on the terminal block, on that IN1-IN16
channel it is displayed in the device web interface.
The sensor comes with a non-detachable cable with lugs at the ends.
The cable length can be increased by
using
, which are connected in series into each other, or independently using any wire with a
cable section of at least 0.4 mm2. The maximum permissible loop length is 100 meters.
The number of connected smoke detectors (mod. M206-5E) is limited only by the number of free IN lines.
Wire
Terminal
Red
+12V
Black
GND
Green
Одна из
OUT
линий
– 1 - 16
White
GND