![NetPing Input+Relay R404 User Manual Download Page 11](http://html.mh-extra.com/html/netping/input-relay-r404/input-relay-r404_user-manual_1674600011.webp)
[ENG] NetPing Input+Relay R404, User guide -[ENG] 4. [DKST 57]Device overview and main features
[ENG] 4. [DKST 57]Device overview and main features
–
Parameter
Value
DAC
1 pcs.
Connector for connecting the battery DK ST
85
P20J1L-04 - 1 pcs.
SNMP control
SNMP v1
SNMP TRAP notifications
SNMP v1/v2
Input lines
16 lines
Type of control of output discrete signals
Electromechanical relays of the SPDT type
Output lines
4 lines
Output relays
4 relay outputs (NC-C-NO, 24VDC 500
мА
, 24VAC 1
А
)
Output analog line (DAC)
1 line (0V - 12V, the maximum output current is not more than
10mA)
Log "1"
at least 8.3 V
Log "0"
not more than 3.7 V
Connector RS485/RS232 (TCP-COM)
1 connector
Power Supply Plug type
DJK-02A
Weight
250 g. (without power supply
Operating temperature range
-30 C to +50 C (without moisture condensation, normal air
humidity)
Output voltages
5V 300mA to power external sensors and 1-wire, 12V 250mA to
power external sensors, including IO and 1-wire