7
To program the ReLAy OUTPUT to operate by PANIC/TAMPeR signals.
Relay oUtPUt oPeRatIon
1
O
n
2
3
4
5
Program Mode
ON/ALARM Pulses relay
PANIC/TAMPR Pulses relay
AUX Pulses relay
LOW BATT Pulses relay
Operating Mode
ON/OFF/ALRM
Latches relay
PANIC/TAMPR Toggles relay
AUX Toggles relay
LOW BATT Latches relay
1
O
n
2
3
4
5
Program Mode
ON/ALARM Pulses relay
PANIC/TAMPR Pulses relay
AUX Pulses relay
LOW BATT Pulses relay
Operating Mode
ON/OFF/ALRM
Latches relay
PANIC/TAMPR Toggles relay
AUX Toggles relay
LOW BATT Latches relay
PANIC Button > Relay
toggles On/Off
PANIC Button = Relay
Pulses 2sec
TAMPeR > Relay toggles
On/Off
TAMPeR > Relay Pulses 2sec
This applies to Ness
transmitters with a tamper
switch, such as LUX Radio
PIR, RR1 Radio Reed
This applies to Ness
transmitters with a tamper
switch, such as LUX Radio
PIR, RR1 Radio Reed
SIgNAL TyPe
PANIC/TAMPeR
ReLAy MODe
TOggLe
ReLAy ACTION
Panic/Tamper signal:
Toggle On/Off
SWITCh SeTTINgS
Switch 3 off, Switches
2, 4, 5 must be on
SIgNAL TyPe
PANIC/TAMPeR
ReLAy MODe
PULSe
ReLAy ACTION
Panic/Tamper signal:
Pulse
SWITCh SeTTINgS
Switch 3 on, Switches
2, 4, 5 off
OPeRATION
OPeRATION
OPeRATION TABLe 3
OPeRATION TABLe 4