Ness M1KAM Quick Start Manual Download Page 2

Page 2

INSTALLING THE ELK-M1KAM

Mount the M1KAM within 10 Metres of the door being controlled.  Since It connects to the 4-wire keypad data bus the M1KAM can be
located from the control up to the maximum distance of the data bus.  The location should have an ambient temperature range
between 0

°

 to 49

°

 C (32° to +120

°

 F).  CAT5 or CAT6 wire (4 pair, 8 conductor) is recommended for all data bus cables as the spare

wires may be required for data return paths where multiple homeruns or devices are installed.  

NOTE: Refer to the  M1 or EZ8 Installa-

tion Manual for information about Data Bus termination when multiple homerun cables are installed.

 

 

Recommended min. conductor

size is 22 or 24 gauge.  Maximum resistance per wire is 25 Ohms. 

DO NOT SPLICE OR CONNECT WIRES WITH THE CONTROL POWER

ON.

Wiring Connections:

1. Turn OFF all power on the M1 or  M1EZ8 Control before making any wiring connections.

2. Connect the 4-wire data bus  

+12V

Data A

Data B

, and 

Neg

 wires coming from the M1 or  EZ8 to the identically marked terminals labeled

M1 DATA BUS

 on the M1KAM.  NOTE: The M1KAM features unpluggable terminals blocks for ease and installation and service.

3. Install a separate local power supply for the locking device (door strike or mag lock).

NEVER attempt to power an electric door strike or mag lock from the +12VDC of the M1/EZ8 Data Bus.

4. The 

Relay 

(Output) on the M1KAM operates as an On/Off switch between the locking device and the power source.   Depending on how

the wiring is connected the voltage to the locking device can either be "turned On" or "turned off" when the Relay (Output) becomes
energized.  Connect the wires in one of the following manners:

Cut one of the two wires leading from the power source to the locking device.  Strip and connect one end to the 

RELAY COM

 terminal.

N/C - If the locking device is "Fail Safe" (unlocks when power removed), connect the other end of the wire to the 

RELAY N/C

 terminal.

N/O - If the locking device is "Fail Secure (stays locked until power applied), connect the other end of the  wire to the 

RELAY N/O

 terminal.

Important points to follow:

1) A 

general purpose blocking diode (supplied) MUST BE INSTALLED 

on Door Strikes (at the strike) across the + and - connections

as shown in the hookup diagram.  This helps stop voltage kickback 'transient' when the strike coil releases.

2) The M1KAM requires a Whenever/And/Then Rule to be written using the NessRP software.  The rule instructs the Relay (Output)

on a specific M1KAM module to energize when a valid access credential (card, fob is read.  See page 5 for an example of an M1
Access Rule.

3) The Output ID (Identification) of the 

Relay

 (Output) on the M1KAM is based on the Data Bus Address of the M1KAM.  See Table 1

under "Setting the Data Bus Address" for more details.

5. Install a proximity reader ("26 BIT" Wiegand compatible) reader and connect it to the M1KAM as follows:

- 26 Bit Wiegand Reader

 - Requires a 4 wire connection, 2 for power and 2 for data to the M1KAM.  Ideally the reader should be powered

from the local power supply being used for the locking device.  It is important for the Negative (-) sides of both power sources (M1/EZ8
Data bus power and local power supply) to be commonly connected.  See wiring diagram.

* Some readers have LED indicators for features like status, armed, ready, etc.  It may be possible to connect and utilize these with
the M1KAM.  See step 8 and the wiring diagram or contact Ness Technical Support for details.

6. Install a Normally Closed (N/C) alarm contact on the door.  Connect this to the M1KAM using a two conductor wire.  One wire connects

to the terminal marked 

IN2DOOR

,  the other connects to one of the terminals marked 

NEG

.  Install a 2,200 Ohm end of line (EOL) resistor

(provided) in series with the switch.  There are two (2) NEG terminals on the M1KAM.  See wiring diagram on opposite page.

Important point to remember:

1) The Zone number (ID) associated with the 

IN2 DOOR

 (door status) input on the M1KAM is based on the Data Bus Address of the

M1KAM.  See Table 1 under "Setting the Data Bus Address" for more details.  From the control panel programming this same input
ID can be defined as a Burglar alarm zone, allowing the door switch to be used for both the alarm and the Access Module.

7. Install a Request to Exit ( RTE) sensor or switch.  This is generally required by law to allow  free exit from the building.  The output from

an RTE device is typcially the same as a two wire N/C door switch.  One wire connects to the terminal marked 

IN1 RTE

, the other connects

to one of the two terminals marked 

NEG

.  Install a 2,200 Ohm end of line (EOL) resistor (provided) in series with the switch.  There are

two (2) NEG terminals on the M1KAM.  See wiring diagram on opposite page.

8. There are three (3) additional Outputs on the M1KAM.  

OUT1 ALARM

 is designed to allow a local alarm if the door is held open too long.

OUT2 READY

 is a remote Ready To Arm indication of the Area or partition which the M1KAM is assigned.   

OUT3 ARM

 is a remote Armed

indication of the Area or partition which the M1KAM is assigned.  Each of these outputs is 12 VDC low current (50mA.), switched negative.
See wiring diagram on opposite page.   Be carefully to NOT EXCEED the maximum drive current of each output.

9. Turn on the power to the control along with the local power source for the locking device and reader.  Proceed to the section  titled "Setting

the Data Bus Address and Enrolling Data Bus Modules".

Summary of Contents for M1KAM

Page 1: ...nects to the 4 wire keypad data bus in place of a traditional M1 Keypad Since the maximum number of keypads on an M1 or M1EZ8 is 16 the maximum number of M1KAM modules and controlled doors is 16 minus any installed keypads Even though an M1 Keypad can accept a 26 bit access reader the M1KAM is a more powerful and less expensive access solution For example the M1KAM includes a relay door unlock out...

Page 2: ...Identification of the Relay Output on the M1KAM is based on the Data Bus Address of the M1KAM See Table 1 under Setting the Data Bus Address for more details 5 Install a proximity reader 26 BIT Wiegand compatible reader and connect it to the M1KAM as follows 26 Bit Wiegand Reader Requires a 4 wire connection 2 for power and 2 for data to the M1KAM Ideally the reader should be powered from the loca...

Page 3: ...Page 3 ...

Page 4: ...HO Time 20 Seconds 10 RTE Time 20 Seconds DHO Time 40 Seconds 01 RTE Time 30 Seconds DHO Time 60 Seconds 11 RTE Time 45 Seconds DHO Time 90 Seconds Enrolling the M1KAM with the control Once the address is set and the M1KAM powered up it will be necessary to manually ENROLL the new device so that the M1 Control knows it is present This is accomplished either from keypad programming Menu 1 Bus Modul...

Page 5: ...tial is rejected the Keypad will produce a low error tone and display Code Not Authorized Redo The most common causes for rejection are A The credential has already been enrolled duplicate codes are not allowed or B The facility code in the credential is not the same brand or is not compatible with the reader Some manufacturers credentials are not readable by other brands of readers 9 After the cr...

Page 6: ...CESS are both enabled Whenever And Then Rules As mentioned above an ACCESS event flag does not actually do anything other than log unless there has been a Whenever And Then Rule written to tell the control what it is suppose to do Rules are written using the ElkRP Programming Software An Access event can be used to create virtually any desired reaction i e turn on an output a light close open a re...

Reviews: