background image

- 8 -

Drain

Ensure the temperature of the bath fluid is safe before draining the unit.

The unit is equipped with a drain located at the back of the unit at the base of

the bath. The drain has ¼" MPT and is capped with a stainless steel plug. To

drain the reservoir simply remove the cap.

To assure proper fit when replacing the cap, be sure to line the threads with

1½ turns of Teflon

® 

tape.

Fluids

Never use flammable or corrosive fluids with this unit.

The selected fluid must have a viscosity of 50 centistokes or less at the

lowest operating temperature.

Filtered tap water is the recommended fluid for operation from +8°C to +80°C.

See Water Quality Standards and Recommendation on the next page.

For operation from -30°C to +8°C, a 50/50 mixture, by volume, of tap water

and laboratory grade ethylene glycol is suggested.

Above +80°C and below -30°C, the user is responsible for fluids used.

Never use pure ethylene glycol as a bath fluid.  Above 80°C the user is

responsible for the fluid used.

Filling

Requirements

The bath work area has a high and low level marker to guide filling. The

markers are 1 inch horizontal slits located in the center of the stainless steel

baffle separating the work area and the pump assembly. The correct fluid

level falls between these two markers. The heating and cooling coils will be

exposed and may become damaged if the correct fluid level is not provided.

When pumping to an external system, keep extra fluid on hand to maintain

the proper level in both the circulating lines and the external system.

Never run the unit when the work area is empty.

Summary of Contents for RTE-111

Page 1: ...nce or to any unit that has been operated or maintained in any way contrary to the operating or maintenance instructions specified in NESLAB s Instruction and Operation Manual This warranty does not c...

Page 2: ...ns 9 SECTION IV Temperature Controller Start Up 10 Controller Keypad Display 10 Changing a Value 11 Controller Displays 11 Operator s Loop 12 Setup Loop 13 Error Messages 15 Autorefill Optional 16 Hig...

Page 3: ...ted and found to be in good condition If the unit shows external or internal damage or does not operate properly contact the transportation company and file a damage claim Under ICC regulations this i...

Page 4: ...sible for the fluid used For 220 240 volt units supplied without a line cord use a harmonized HAR grounded 3 conductor cord type H 0 5 V V F with conductors listed below A suitable cord end is require...

Page 5: ...1 x 20 3 x 15 3 9 1 4 x 10 x 6 23 5 x 25 4 x 15 2 9 1 4 x 10 x 9 23 5 x 25 4 x 22 9 1 9 7 0 3 2 12 25 5 4 20 5 25 x 10 5 16 x 15 7 8 63 5 x 26 2 x 40 3 25 x 12 3 8 x 18 3 8 63 5 x 31 4 x 46 7 27 7 8 x...

Page 6: ...m ambient temperature of 95 F In terms of Celsius derate the cooling capacity 1 for every 0 5 C above 24 C to a maximum ambient temperature of 35 C Electrical Requirements Line voltage may be easily a...

Page 7: ...unit and the external system as short as possible and to use the largest diameter tubing practical Tubing should be straight and without bends If diameter reductions must be made make them at the inl...

Page 8: ...usted the pump inlet will draw an occasional air bubble to prevent over flow and the pump outlet will force fluid through the submerged tube to prevent aeration of the vessel To avoid siphoning the ba...

Page 9: ...page For operation from 30 C to 8 C a 50 50 mixture by volume of tap water and laboratory grade ethylene glycol is suggested Above 80 C and below 30 C the user is responsible for fluids used Never use...

Page 10: ...ystem Although the initial fill may be as high as 10 megohm cm compensated at 25 C the desired level for long time usage is 1 to 3 megohm cm compensated at 25 C The above two recommendations will redu...

Page 11: ...on The HEAT indicator flashes when the heater is pulsating A balance between COOL and HEAT controls the temperature NOTE Below 50 C the refrigeration system is on unless the setpoint is more than 2 C...

Page 12: ...plays An alphanumeric display presents numeric readings of various operating conditions within the bath Display function is selected by pressing the appro priate keys to move through a menu of availab...

Page 13: ...id temperature Press the NEXT ENTER key to view the setpoint SP displays the controller setpoint The display will flash between SP and the actual setpoint number Use the YES NO keys to change the setp...

Page 14: ...etup Loop if any key is not pressed during a one minute time span the controller will automatically return to the Operator s Loop tempera ture display NOTE If the unit exceeds either temperature limit...

Page 15: ...oop 2 of 2 Hit High Temperature Limit Lot Low Temperature Limit r232 RS232 Protocol bAUd BAUD rate factory value 9600 dAtA Data Bits factory value 8 StoP Stop Bit factory value 1 PAr Parity factory va...

Page 16: ...04 13 Interrupt Error Er14 Synchronous Error Er15 Asychronous Error Er16 Bad Calibration Er19 Low Temp Limit Er21 High Temp Limit Er23 RTD2 Shorted Er24 RTD2 Open Not Installed Er25 RTD1 Shorted Er26...

Page 17: ...e plumbing connection for the autorefill device labeled WATER INLET is located on the rear of the autorefill assembly The connection is 3 8 inch OD stainless steel Remove the nut and install the tubin...

Page 18: ...L SAFETY adjustment dial on the right side of the pump box Turn the dial fully clockwise and press the red RESET switch located next to the adjustment dial NOTE On units without a reset switch turn th...

Page 19: ...nsor Connections Pin Function 1 3 wire RTD connection A 2 No connection 3 No connection 4 3 wire RTD connection B 5 No connection 6 No connection 7 No connection 8 No connection 9 3 wire RTD connectio...

Page 20: ...denser will lead to a loss of cooling capacity Periodic vacuuming of the condenser is necessary To access the condenser the front grille must be removed The unit must be turned off before the front pa...

Page 21: ...screws two on each side securing the reservoir s cover To get slack on the refrigeration cable remove the cable strap The cable itself does not need to be disconnected Turn the cover assembly over an...

Page 22: ...or s loop Calibration loop Setup loop tunE C A L Chip Number Software Number Software Version Checksum Code N O N O HOLD N O HOLD 10 SECS N E X T E N T E R N E X T E N T E R N E X T E N T E R N E X T...

Page 23: ...or s Setup and Calibration Loops Go to the Setup Loop and place the unit in the internal or remote RTD mode of operation RTD1 Internal Probe RTD2 Remote Probe Return to the Operator s Loop adjust the...

Page 24: ...23 Figure 4 Calibration Loop rtd1 Internal sensor rtd2 remote sensor r1H High temperature r1L Low temperature Ain NA for this unit Aout NA for this unit Stor Store...

Page 25: ...or will short cycle clicking sound and no cooling will occur Proper ventilation is required for heat removal Make sure ventilation through the front and rear panels is not impeded and the panels are f...

Page 26: ...r based temperature control apparatus Choose upper or lower temperature limits and monitor system status with an alarm NEScom can also record your results on a user selectable graph NesCom must be use...

Page 27: ...cambiar el fluido refrigerante suba la temperatura de operaci n de la unidad para descongelar los serpentines de refrigeraci n Es necesario un vaciado peri dico de las aletas del condensador La frecue...

Reviews: