WP-Series Reverse Osmosis System
Installation Instructions and User Manual
Page | - 24 -
Adjustment Of Pressure Switch
CAUTION:
Pressure switch has been factory pre-set to 8 psi. This switch should not be adjusted unless
recommended by factory.
CAUTION:
220 Volt Shock Hazard.
Tools
Required: Flat Blade Screwdriver.
Turn off R.O. unit and disconnect all electrical power prior to removing cover plates on pressure switches.
Low Pressure Cut-Out Switch
1. Loosen nut and remove cover plate.
Illustration 15- Pressure Switch Adjustment
2. Use box wrench to adjust nut on left side counterclockwise to lessen pressure; clockwise to raise pressure.
3. Do not tamper with nut on right side.
4. Replace cover.