background image

 

Standalone Wall-Mount Controller  

Specification and Installation Instructions 

 

www.neptronic.com 

 

Page | 29

 

Sensor Offset Menu 

This menu is accessible through normal operation mode. The Mode Selector Jumper (JP1) must be set to the RUN position 
(Operation Mode). 
 
1.  Press the 

 and 

 keys for 5 seconds. The 

“Enter Password”

 screen appears. 

2.  Enter the password (

372

) within 1 minute. Use

 

the 

 and

 arrow keys to increase or decrease the value and the 

,

 

buttons to toggle between the digits. If

 

you enter the wrong password, the controller displays “

Eror

” and returns to Operation 

Mode.  

Use the same menu operations as described in Programming Mode on page 4. 
 
The controller will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not 
press any key for 5 minutes. The changed values will be saved automatically. 

 

“Intern

 

Temp Sensor Offset”

 

 

 

Range: 

 

Offset: 
Increment: 

0ºC to 50ºC   

[32ºF to 122ºF] 

Max. ± 5ºC 

 

[± 9ºF] 

0.1ºC    

 

 

[0.2ºF] 

Compare the displayed temperature reading with a known value from a thermometer or other temperature  sensing device. To 
offset or calibrate the sensor, use the arrow buttons to set the desired temperature reading. This is useful for controllers installed 
in areas where the temperature read is slightly different than the room’s actual temperature. For example, a controller placed 
right under the air diffuser.  

 

“Extern Temp

 

Sensor Offset”

 

 

 

Range: 

 

Offset: 
Increment: 

-40.0ºC to 100ºC  [-40ºF to 212ºF] 
Max. ± 5ºC 

 

[± 9ºF] 

 0.1ºC   

 

 

[0.2ºF] 

This option appears only if you have selected 

t10.0 

or 

t10V 

at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". The 

display shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value 
(e.g. thermometer). If the sensor is not connected or short circuited, the unit displays the sensor's limit. 

 

"Extern Humidty Sensor Offset" 

 

 

Offset: 
Range: 

 

Increment: 

± 5% 
10% RH to 90% RH 
0.1% RH 

 

This option appears if the controller is set to use an external humidity sensor. The display shows the relative humidity 
percentage read by the external humidity sensor. Adjust the offset by comparing it with a known value humidistat. If the sensor 
is not connected or short circuited, unit displays the sensor's limits. The humidify 

 symbol is also displayed. 

 

"VFD Pressur Setpnt" 

 

 

 

Default: 
Range: 
Increment: 

500 Pa 
100 to pressure maximum range 
1 Pa

 

This option appears only if you have selected 

VFdP 

at Step 17 "AO2 Ramp", and 

P10V

 at Step 80, "UI1 Signal Type" or Step 

84, "UI2 Signal Type". Select the setpoint value for VFD pressure. The fan 

 symbol is also displayed. 

 

"VFD Temp Setpnt"

 

 

 

Default: 
Range: 
Increment: 

22.0ºC  

 

 

[72ºF]

 

 10.0ºC to 40.0ºC  [50ºF to 104ºF] 

0.5ºC    

 

 

[1ºF] 

This option appears only if you have selected

 VFdt

 at Step 17 "AO2 Ramp". Select the setpoint value for VFD pressure. The 

fan 

 symbol is also displayed. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for TSU00 Series

Page 1: ...nctionality for the terminal device TSU00 Series Features Fan control 1 2 or 3 speed auto on or analog ECM Optional internal external humidity sensor input for simple and accurate humidity control Deh...

Page 2: ...uts 2 Universal Inputs 0 10Vdc 10K sensor dry contact Outputs 5 Binary Outputs OptoFET 250mA max 2 Analog Outputs 0 10Vdc adjustable Power supply 22 to 26 Vac 50 60Hz Power consumption 1 VA max Propor...

Page 3: ...3 select any ramp Fan speed 3 8 BO5 Heat W2 Fan speed 2 Fan speed 2 select any ramp Fan speed 2 Fan speed 2 9 BO6 Fan speed 1 Fan speed 1 Fan speed 1 select any ramp Fan speed 1 Fan speed 1 Fan speed...

Page 4: ...holding the base and the front cover of the unit together B Lift the front cover of the unit to separate it from the base C Pull all wires through the holes in the base D Secure the base to the wall u...

Page 5: ...minimum user point The minimum value is restricted by the maximum value set at Step 3 Maximum User Setpnt In other words the value that is set as the minimum cannot be greater than the maximum value M...

Page 6: ...emand StP RH C temperature humidity setpoint and cooling heating demand Select the desired information to appear on the display Keypad Lock Settings Keypad Upper Left Locked Default Range No Disable y...

Page 7: ...ble options Cr1 Cooling Ramp 1 or Cr2 Cooling Ramp 2 The Cr1 and Cr2 ramps are used for cooling If selected the controller performs cooling based on the cooling proportional integral and dead band val...

Page 8: ...span value for the AO2 ramp The maximum value is restricted by the minimum value at Step 18 AO2 Minimum Voltage In other words the maximum value should not be less than the minimum value AO2 Dirrev D...

Page 9: ...le If you select FAN Step 28 Fan Spd Signal will not be available Cr1 Cr2 Hr1 Hr2 with fan Hr2 without fan CH1 HU CO2 6w dto OFF Cor AO3 Minimum Voltage Default Range Increment 0 0 Volt 0 0 to 10 0 Vo...

Page 10: ...ode option is not available in Control Mode The fan symbol is also displayed Hide Fan Display Info Default Range No Disable yES Enable No Disable Select to enable or disable the fan display informatio...

Page 11: ...regularly If another output is set to heat it performs heating regularly HU Humidify If selected the controller modulates the output based on the humidify demand CO2 Carbon dioxide If selected the co...

Page 12: ...Default Range Increment 20 of the demand 15 to 80 1 This option does not appear if the signal ramp for BO4 is set to OFF Step 42 BO4 Ramp Select the percentage at which you want BO4 to close at of de...

Page 13: ...Ramp Set the direction of the binary signal to either Direct or Reverse BO5 Contact Delay Minutes Default Range Increment 0 minute 0 to 15 minutes 1 minute This option does not appear if the signal ra...

Page 14: ...inutes 1 minute This option does not appear if the signal ramp for BO6 is set to OFF Step 54 BO6 Ramp Select the closing delay for BO6 output BO6 Signal Type Default Range OnOF On Off tPm Pulsing OnOF...

Page 15: ...9 F 0 5 C 1 F Select the desired proportional band value of the changeover ramp The cooling and heating symbols are also displayed CH Over Dead Band Default Range Increment 0 3 C 0 6 F 0 0 C to 5 0 C...

Page 16: ...ompressor set the delay in minutes before activating or reactivating the cooling output The cooling symbol is also displayed Heating Intgral Time In Seconds Default Range Increment 0 seconds 0 to 250...

Page 17: ...en Mode and 109 Door Fan Mode will be available dFt If selected the controller activates an alarm to indicate that the filter is dirty FLS If selected the controller activates an alarm to indicate tha...

Page 18: ...win door dFt FLS oVht SEL at Step 80 UI1 Signal Type Set the delay in seconds before the state of input for UI1 is changed Universal Input 2 UI2 UI2 Signal Type UI2 Default Range OFF OFF t10 0 SENs n...

Page 19: ...the minimum cannot be greater than the maximum value Extern Temp Maximum Default Range Increment 50 C 122 F 50 C to 100 C 122 F to 212 F 0 5 C 1 F This option appears only if you have selected t10V at...

Page 20: ...80 UI1 Signal Type or Step 84 UI2 Signal Type Pressur Maximum Range Default Range Increment 2000 Pa 200 to 200 0 Pa 50 Pa This option appears if you have selected P10V at Step 80 UI1 Signal Type or St...

Page 21: ...seconds The fan symbol is also displayed VFD Temp Control Source Default Range itS internal itS internal EtS External Select the source for VFD temperature control itS If selected the controller will...

Page 22: ...0 The moon symbol is displayed to indicate Night Set Back NSB Mode NSB Fan Mode Default Range AUto Automatic AUto Automatic LO Low mEd Medium HI High This option appears only if you have selected nSb...

Page 23: ...e Default Range StP Setpoint override enabled StP Setpoint override enabled OFF This option appears only if you have selected OCC at Step 80 UI1 Signal Type or Step 84 UI2 Signal Type The moon symbol...

Page 24: ...ic humidify and dehumidfy If selected the ramp of atleast one analog or binary must be set to Hu humidify and another output must be set to COOl cooling dEHU Dehumidify only If selected the ramp of at...

Page 25: ...ement 30 RH 10 RH to 65 RH 0 5 RH This option appears only if you have selected AuTo Hu or deHU at Step 123 Humidty Control Mode and also nSb at Step 80 UI1 Signal Type or Step 84 UI2 Signal Type Adju...

Page 26: ...ally when the temperature drops to 4 C 39 F even if the controller is in Cooling or OFF mode Once the temperature reaches 5 C 41 F the heating stops Delta Temperature Enable Delta Temp Mode Default Ra...

Page 27: ...in Programming Mode on page 4 The controller will return to normal mode if you navigate through the entire menu and do not make any selection or if you do not press any key for 5 minutes The changed v...

Page 28: ...ule Schedule 9 Select Day of Week Default Range mo mo Monday tu Tuesday wE Wednesday th Thursday Fr Friday SA Saturday Su Sunday Select the day of the week 10 E1 00 00 Range Increment E1 to E6 00 to 2...

Page 29: ...For example a controller placed right under the air diffuser Extern Temp Sensor Offset Range Offset Increment 40 0 C to 100 C 40 F to 212 F Max 5 C 9 F 0 1 C 0 2 F This option appears only if you hav...

Page 30: ...If a sensor is disconnected or short circuited then the unit displays the sensor s limits To toggle the temperature scale between C and F press both the up and down arrow keys for 3 seconds Temperatu...

Page 31: ...Mode Press any key to override NSB for the delay defined at Step 110 NSB Overide Delay Minutes The symbol flashes to indicate that the NSB mode is overridden during this time the standard setpoints ar...

Page 32: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Reviews: