Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 13
Binary Output 5 (BO5)
The Binary Output 5 settings appear only if you have selected either fan speed 1 at Step 28, "Fan Spd Signal" or VFdP,
VFdt or FAN at Step 17, "AO2 Ramp".
"BO5 Ramp"
Default:
Range:
OFF
Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr
Select the desired ramp from the available options. Same as BO3 options.
If you select
OFF
, Steps 49 to 52 will not be available.
"BO5 Close Percent"
Default:
Range:
Increment:
20% of the demand
15 to 80%
1%
This option does not appear if the signal ramp for BO5 is set to
OFF
(Step 48, "BO5 Ramp"). Select the percentage at which
you want BO5 to close (at % of demand of the ramp selected at Step 48, "BO5 Ramp").
"BO5 Open Percent"
Default:
Range:
Increment:
0% of the demand
0 to (BO5 Close)-4%
1%
This option does not appear if the signal ramp for BO5 is set to
OFF
(Step 48, "BO5 Ramp"). Select the percentage at which
you want BO5 to open (at % of demand of the ramp selected at Step 48, "BO5 Ramp").
"BO5 Dirrev"
Default:
Range:
dir (Direct)
dir (Direct), rEV (Reverse)
This option does not appear if the signal ramp for BO5 is set to
OFF
(Step 48, "BO5 Ramp"). Set the direction of the binary
signal to either Direct or Reverse.
"BO5 Contact Delay Minutes"
Default:
Range:
Increment:
0 minute
0 to 15 minutes
1 minute
This option does not appear if the signal ramp for BO5 is set to
OFF
(Step 48, "BO5 Ramp"). Select the closing delay for BO5
output.
“BO5 Signal Type”
Default:
Range:
OnO
F
(On/Off)
tPm (Pulsing), OnO
F
(On/Off), FLot (Floating)
This option does not appear if the signal ramp for BO5 is set to
OFF
(Step 48, "BO5 Ramp"). Select the signal type for BO5 to
either Pulsing, On/Off or Floating.
Binary Output 6 (BO6)
The Binary Output 6 settings appear only if you have selected either FAN, VFdt or VFdP at Step 17, "AO2 Ramp".
"BO6 Ramp"
Default:
Range:
OFF
Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, 6w, dto, VFdt, VFdP, OFF,
COr
Select the desired ramp from the available options. Same as BO3 options. The VFdt and VFdP options are available only if you
have selected them at Step 17, "AO2 Ramp".
If you select
OFF
, Steps 55 to 58 will not be available.
•
6W (6-way Valve). If selected, the controller will modulate the 6-way valve depending on the heating or cooling demand.
•
dto (Delta temperature control). If selected, the controller will modulate the
ΔT control based on the inlet and outlet
temperature of the water inside the fan coil unit.
•
VFdt (VFD Temp Loop). If selected, the controller will modulate the VFD fan based on the selected temperature input.