SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 8
Output Specifications
Table
2 -
Output Specifications (120V models)
72
°
F (22
°
C)
Entering
temperature
Entering RH:
10%RH
20%RH
30%RH
40%RH
CFM
(m
3
/h)
Humidification Cooling Humidification Cooling Humidification Cooling Humidification Cooling
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
1250
(2124)
26.5
(12)
28.2
(8.3)
22.7
(10.3)
24.1
(7.1)
19.3
(8.8)
20.4
(6)
15.9
(7.2)
16.8
(4.7)
2500
(4248)
52.9
(24)
56.3
(16.5)
45.3
(20.5)
48.2
(14.1)
38.5
(17.5)
40.9
(12)
31.8
(14.4)
33.8
(9.3)
5000
(8495)
104.9
(47.6)
112.6
(33)
90.6
(41.1)
96.3
(28.2)
77.1
(35)
81.8
(24)
63.6
(28.8)
67.4
(18.6)
Leaving condition:
78%RH
52
°
F
(11
°
C)
82%RH
54
°
F
(12
°
C)
85%RH
57
°
F
(14
°
C)
88%RH
60
°
F
(16
°
C)
85
°
F (29
°
C)
Entering
temperature
Entering RH:
10%RH
20%RH
30%RH
40%RH
CFM
(m
3
/h)
Humidification Cooling Humidification Cooling Humidification Cooling Humidification Cooling
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
1250
(2124)
32.3
(14.7)
34.2
(10)
27.2
(12.3)
28.8
(8.4)
22.9
(10.4)
24.2
(7.1)
18.8
(8.5)
19.8
(5.8)
2500
(4248)
64.5
(29.3)
68.3
(20)
54.3
(24.6)
57.5
(16.9)
45.8
(20.8)
48.4
(14.2)
37.4
(17)
39.4
(11.5)
5000
(8495)
128.9
(58.5)
136.7
(40.1)
108.7
(49.3)
115
(33.7)
91.7
(41.6)
96.8
(28.4)
74.8
(33.9)
78.9
(23.1)
Leaving condition:
76%RH
60
°
F
(16
°
C)
80%RH
64
°
F
(18
°
C)
85%RH
67
°
F
(19
°
C)
87%RH
70
°
F
(21
°
C)
Note: Humidity output for high RH entering conditions may be less than the above values calculated
with an evaporation factor for air at 50%RH.
Table
3 -
Output Specifications (208 to 240V models)
72
°
F (22
°
C)
Entering
temperature
Entering RH:
10%RH
20%RH
30%RH
40%RH
CFM
(m
3
/h)
Humidification Cooling Humidification Cooling Humidification Cooling Humidification Cooling
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
1500
(2549)
31.8
(14.4)
33.8
(9.9)
27.2
(12.3)
28.9
(8.5)
23.1
(10.5)
24.5
(7.2)
19.1
(8.7)
20.2
(5.9)
3000
(5097)
63.5
(28.8)
67.6
(19.8)
54.4
(24.7)
57.8
(16.9)
46.2
(21)
49.1
(14.4)
38.2
(17.3)
40.5
(11.9)
6000
(10194)
125.9
(57.6)
135.1
(39.6)
108.7
(49.3)
115.5
(33.8)
92.5
(42)
98.1
(28.8)
76.3
(34.6)
80.9
(23.7)
Leaving condition:
78%RH
52
°
F
(11
°
C)
82%RH
54
°
F
(12
°
C)
85%RH
57
°
F
(14
°
C)
88%RH
60
°
F
(16
°
C)
85
°
F (29
°
C)
Entering
temperature
Entering RH:
10%RH
20%RH
30%RH
40%RH
CFM
(m
3
/h)
Humidification Cooling Humidification Cooling Humidification Cooling Humidification Cooling
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
lbs/h
(kg/h)
kBTU/h
(kW)
1500
(2549)
38.7
(17.6)
41
(12)
32.6
(14.8)
34.5
(10.1)
27.5
(12.5)
29
(8.5)
22.5
(10.2)
23.7
(6.9)
3000
(5097)
77.4
(44.6)
82
(24)
65.2
(29.6)
69
(20.2)
55
(24.9)
58.1
(17)
44.9
(20.4)
47.3
(13.9)
6000
(10194)
154.7
(70.2)
164
(48.1)
130.5
(59.2)
138
(40.4)
110
(49.9)
116.2
(34)
89.8
(40.7)
94.7
(27.8)
Leaving condition:
76%RH
60
°
F
(16
°
C)
80%RH
64
°
F
(18
°
C)
85%RH
67
°
F
(19
°
C)
87%RH
70
°
F
(21
°
C)
Note: Humidity output for high RH entering conditions may be less than the above values calculated
with an evaporation factor for air at 50%RH.