SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 36
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Physical IO
ControlInput
[6]
Does not appear if ControlProfile is set to InternHumNetwork,
InternCoolNetwork, HRL Hum or HRL Cool.
Signal:
0.000V
* (min: 0.000V, max: 15.000V)
Displays the value of the humidity demand control analog input signal.
ControlInput:
0.0%
or
68°F
[20.0
°
C]
* (min: 0.0%, max: 100.0%)
or
* (min: -40.0°F, max: 302.0°F)
* [min: -40.0°C, max: 150.0°C]
Units: C, F
Displays the actual value of the humidity demand control analog input.
(Values are displayed in °C or °F when ControlProfile is set to
InternCoolAnalog.)
Min:
0.0%
or
32°F
[0.0
°
C]
min: 0.0%, max: 100.0%
or
* (min: -40.0°F, max: 302.0°F)
* [min: -40.0°C, max: 150.0°C]
Units: C, F
Set the minimum value of the humidity demand control analog input.
(Values are displayed in °C or °F when ControlProfile is set to
InternCoolAnalog.)
Max:
100.0%
or
104°F
[40.0
°
C]
min: 0.0%, max: 100.0%
or
* (min: -40.0°F, max: 302.0°F)
* [min: -40.0°C, max: 150.0°C]
Units: C, F
Set the maximum value of the humidity demand control analog input.
(Values are displayed in °C or °F when ControlProfile is set to
InternCoolAnalog.)
Bias:
0.0%
or
0.00
∆°F
[0.00
∆°C]
min: -10.0%, max: 10.0%
or
min: -
18.00∆°F, max: 18.00∆°F
[min: -
10.00∆°C, max: 10.00∆°C]
Units: ∆°C, ∆°F
Set the bias value for the humidity demand control analog input.
(Values are displayed in
∆
°C or
∆
°F when ControlProfile is set to
InternCoolAnalog.)
SignalType:
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
Select the signal type for the humidity demand control analog input.
RoomRH
[6]
Only appears if ControlProfile is set to an InternHumAnalog or
DemandSrc is set to HumRoomDemand.
Signal:
0.000V
* (min: 0.000V, max: 15.000V
Displays the value of the room humidity analog input signal.
RoomRH:
0.0%
* (min: 0.0%, max: 100.0%)
Displays the actual value of the room humidity analog input.
Min:
0.0%
min: 0.0%, max: 100.0%
Set the minimum value of the room humidity analog input.
Max:
100.0%
min: 0.0%, max: 100.0%
Set the maximum value of the room humidity analog input.
Bias:
0.0%
min: -10.0%, max: 10.0%
Set the bias value for the room humidity analog input.
SignalType:
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
Select the signal type for the room humidity analog input.
RoomTemp
[6]
Only appears if ControlProfile is set to an InternCoolAnalog or
DemandSrc is set to TempRoomDemand.
Signal:
0.000V
* (min: 0.000V, max: 15.000V)
Displays the value of the room temperature analog input signal.
RoomTemp:
68°F
[20.0
°
C]
* (min: -40.0°F, max: 302.0°F)
* [min: -40.0°C, max: 150.0°C]
Units: C, F
Displays the actual value of the room temperature analog input.
Min:
32°F
[0.0
°
C]
* (min: -40.0°F, max: 302.0°F)
* [min: -40.0°C, max: 150.0°C]
Units: C, F
Set the minimum value of the room temperature analog input.
Max:
104°F
[40.0
°
C]
* (min: -40.0°F, max: 302.0°F)
* [min: -40.0°C, max: 150.0°C]
Units: C, F
Set the maximum value of the room temperature analog input.
Bias:
0.00
∆°F
[0.00
∆°C]
min: -
18.00∆°F, max: 18.00∆°F
[min: -
10.00∆°C, max: 10.00∆°C]
Units: ∆°C, ∆°F
Set the bias value for the room temperature analog input.
SignalType:
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
Select the signal type for the room temperature analog input.