BM000S/020S/060S/080S
BM800S/820S/860S/880S
Specification & Installation instruction
2
Mechanical installation
CLUTCH
MOUNTING
BRACKET
1.
Manually close the damper blades and positioned the
actuator at 0º or 90º.
2.
Slide the actuator onto the shaft.
3.
Tighten the nuts on the “U” bolt to the shaft with a 8mm
wrench to a torque of 60 in.lb. [6,7 Nm].
4.
Slide the mounting bracket under the actuator. Ensure free
movement of the slot at the base of the actuator. The
bracket pin must be placed in the mid distance of the slot.
5.
Fix the bracket to the ductwork with #8 self-tapping screws.
Wiring Diagrams
Analog 2 to 10 Vdc
1
2
3
COMMON (-)
SUPPLY (+)
2 to 10 VDC
TB1
JP1
Jumper at left
Analog 4 to 20 mA
1
2
3
COMMON (-)
SUPPLY (+)
4 to 20 mA
TB1
JP1
Jumper at right
PC Board
Dip switch settings
Rotation direction (SW1)
CW
(0 to 90º)
CCW
(90 to 0º)
1 2 3
Terminal
TB1
SW
2
Rotation direction
Fail safe direction
(only on model 60S & 80S)
SW1
Potentiometer
JP1
Control signal
selection
BM060VAV
Fail safe direction (SW2)
(only on model 60S & 80S)
Fail safe
return at 0º
Fail safe
return at 90º
Stroke adjustment
To adjust the stroke, move the adjustment screws at the desired position.