SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 12
ID
Name
List
Description
W?
Notes
AV.198
Module 3 Run Time
Integrator
Value of the total runtime of the third humidifier module.
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.199
Module 3 Service On Time
Integrator
Value of the operating time of the third humidifier module, since the last
servicing.
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.200
Module 3 Service Run
Time
Integrator
Value of the runtime of the third humidifier module, since the last servicing.
Present_Value
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.201
Module 3 On Time
Integrator
Value of the total operating time for the third humidifier module
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.202
Module 3 Demand
Integrator
Value of the measured humidity demand of the third humidifier module.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
0% to 100%, Resolution 1.00%
AV.206
Module 3 Max Steam
Output
Integrator
Configuration value of the maximum steam output of the third modulating
humidifier relative to its total capacity.
Present_Value
Out_of_Service
COV_Increment
0% to 100%, Resolution 5.00%
AV.210
Module 4 Chimney Temp
Integrator
Value of the flue gas temperature value of the fourth humidifier module.
Present_Value
Out_of_Service
COV_Increment
32.00°F to 500.00°F or 0.00°C to max: 260.00°C
Resolution 0.18°F or 0.10°C
AV.211
Module 4 Water Temp
Integrator
Value of temperature of water in the evaporation chamber of the fourth
humidifier module.
Out_of_Service
COV_Increment
Units
32°F to 257°F or 0°C to 125°C
Resolution 0.018°F or 0.010°C
AV.212
Module 4 Water
Frequency
Integrator
Value of the input frequency of the water level sensor of the fourth
humidifier module.
Present_Value
Out_of_Service
COV_Increment
0Hz to 30000Hz, Resolution 1Hz
AV.214
Module 4 Ambient Temp
Integrator
Value of the temperature inside of the weather proof enclosure of the
fourth humidifier module.
Present_Value
Out_of_Service
COV_Increment
-40.00°F to 212.00°F or
-40.00°C to 100.00°C
Resolution 0.18°F or 0.10°C
AV.215
Module 4 Fan Feedback
Integrator
Value from the burner fan feedback of the fourth humidifier module,
Present_Value
Out_of_Service
COV_Increment
0 to 2000 Hz, Resolution 1 Hz
AV.216
Module 4 Fan PWM
Integrator
Value of the PWM control signal from the burner fan of the fourth
humidifier module.
Out_of_Service
COV_Increment
Relinquish_Default
0% to 100%, Resolution 0.10%
AV.218
Module 4 Run Time
Integrator
Value of the total runtime of the fourth humidifier module.
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.219
Module 4 Service On Time
Integrator
Value of the operating time of the fourth humidifier module, since the last
servicing.
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours