2. Select the required parameter by pressing the or keys to scroll
through the list of adjustable parameters.
3. Confirm the selection by pressing the
key.
4. Modify the value of the parameter using the or keys.
5. Confirm the new value of the parameter by pressing the
key.
6. Go back to the main display by pressing the
h
key.
For more information, see
Browsing in the menus, page 18
8.2.2
Setting the heating
Caution
The name of the PCB is displayed. Check that it is actually the
PCB on which the setting must be made.
Note
The heating mode can be managed using the TIME PROG menu.
1. Access the heating parameters by pressing the key twice.
Note
If no outside temperature sensor is connected, this menu can be
used to set the temperature of the heating water.
If an outside temperature sensor is connected, this menu can be
used to set the indoor temperature setpoint.
2. Display the parameters for the required circuit by pressing the or
key.
The name of the circuit and the heating water temperature set
point are displayed alternately.
3. Confirm by pressing the
key.
4. Access setting of the heating water temperature set point by press
ing the
key.
5. Set the heating water temperature set point by pressing the or
key.
Note
Press the
h
key to cancel all input.
6. Confirm the new temperature setpoint by pressing the
key.
7. Go back to the main display by pressing the
h
key.
8.2.3
Setting the domestic hot water temperature
Note
Domestic hot water production can be managed via the TIME
PROG sub-menu dedicated to timer programming.
1. Access the domestic hot water production parameters by pressing
the
key twice.
Fig.37
MW
-5
0
0
0
0
4
0
-5
Fig.38
MW-5000144-3
Fig.39
MW-3000249-4
Fig.40
MW-6000254-2
8 Control panel settings IniControl 2
28
EFU FF
7641178 - v02 - 17102016