Mode 3 ~ Mode 12
Mode 3 ~ Mode 12 have various power-on delay and power-off delay. Each
mode supports a hard-off timeout of 10 minutes.
Mode
Power-on Delay
Power-off Delay
Hard-off Timeout
3
10 seconds
10 seconds
10 minutes
4
10 seconds
1 minute
10 minutes
5
10 seconds
5 minutes
10 minutes
6
30 seconds
1 minute
10 minutes
7
30 seconds
5 minutes
10 minutes
8
30 seconds
10 minutes
10 minutes
9
3 minutes
1 minute
10 minutes
10 (A)
3 minutes
10 minutes
10 minutes
11 (B)
3 minutes
30 minutes
10 minutes
12 (C)
10 minutes
30 minutes
10 minutes
⚫
Mode 13 (D) / Mode 14 (E)
Mode 13 and Mode 14 are ignition power control modes with very long
power-
off delay. Both modes support the feature of “smart off
-
delay”, which
automatically detect system status during power-off delay duration and cut off
system power if system is off in prior to power-off delay expired.
Mode
Power-on Delay
Power-off Delay
Hard-off Timeout
13 (D)
30 seconds
2 hours
10 minutes
14 (E)
3 minutes
2 hours
10 minutes
⚫
Mode 15 (F)
Mode 15 is reserved for manufacturer purposes.